Program settings

The appearance of the compatible products' display
differs depending on model. The menu system also
varies.
F-models
Program setting of PVT 40 can be performed via the
start guide or directly in the menu system.

START GUIDE

The start guide appears at first start-up after the heat
pump installation, but can also be found in:
• menu 5.7 for F-models.
• menu 7.7 for S-models.

MENU SYSTEM

If you do not make all settings via the start guide, or if
you need to change any of the settings, this can be done
in the menu system.
S-MODELS
Menu 7.2.1 - Add/remove accessories
Add or remove accessories here.
Select "PVT Source".
Menu 7.1.2.8 - Brine alarm, settings
Here, you can set the lowest and highest temperature
for brine in, as well as the highest temperature at which
the system will initiate an alarm.
Menu 7.2.25 - PVT Source
Here, you can set
• the temperature at which shunt valve (QN41) is to
start working, max. brine in, factory setting: 20°C.
• shunt amplification, factory setting: 1.0.
• shunt waiting time, factory setting: 30 s.
• whether electricity is to be permitted during defrosting
when the valve QN10 is in hot water mode. factory
setting: no. Only applies in the PC models.
Menu 7.5.3 - Forced control
Here, you can control whether the shunt valves (QN41)
and/or (QN10) are to close or open.
PVT 40 | GB
S-models
You can also force start relay K4 on the AXC board.
F-MODELS
Menu 5.2.4 - accessories
Activating/deactivating of accessories.
Select: "NIBE PVT-source".
Menu 5.1.7 -min. brine out
Setting the lowest brine temperature out.
Caution
For optimum operation, the lowest brine tem-
perature should be changed to -12°C, or the
lowest adjustable value.
Menu 5.1.7 -max brine in
Setting the highest brine temperature in.
Menu 5.3.25 -NIBE PVT-source
Here, you can set
• max. brine in, at which temperature the shunt valve
(QN41) will start working, max.
• shunt amplification, factory setting 1.0.
• shunt waiting time, factory setting 30 s.
• whether electricity is to be permitted during defrosting
when the valve QN10 is in hot water mode. factory
setting: no. Only applies in the PC models.
Menu 5.6 - forced control
Forced control of the different components in the heat
pump as well as in the different accessories that may
be connected.
FN2-AA5-K1: No function.
FN2-AA5-K2: Signal (close) to shunt (QN14).
FN2-AA5-K3: Signal (open) to shunt (QN14).
FN2-AA5-K4: No function.
Caution
See also the Installer Manual for the compatible
product.
15