12. Installation of flue
IT
DE
GB
CZ
HU
RO
Downloaded from
www.Manualslib.com
We guarantee ease and flexibility of installation for a gas-fired forced draft boiler thanks to the fittings
and air ducts
and fixtures supplied (described below).
The boiler is especially designed for connection to an exhaust flue / air ducting, with either coaxial,
vertical or horizontal terminal. By means of a splitting kit a two-pipe system may also be installed.
In case exhaust and intake flues not supplied by BAXI S.p.A. have been installed, these must
be certified for the type of use and must have a maximum pressure drop of 100 Pa.
Warnings for the following types of installation:
C
, C
The terminals for the split flue must be provided for within a square with 50 cm sides. Detailed
13
33
instructions are given together with each accessory.
C
The terminals for combustion air intake and for the expulsion of combustion products must
53
not be provided for on opposite walls of the building.
C
The maximum pressure drop of the ducts must not exceed 100 Pa. The ducts must be certified
63
for the specific use and for a temperature of over 100°C. The chimney flue must be certified
in accordance with the prEN 1856-1 Regulation.
C
, C
The chimney or flue used must be suitable for the use.
43
83
Figure 7