TTC25
95
195
TTC25
25A 210-240/380-415V~
Made in Sweden
AB REGIN, Kållered
Power
L1 In
L2 In
L3 In
L3 Out
L2 Out
L1 Out
Signal
1. Neutral
See
2. Wi r i n g
3. link
instructions
4. Main sensor
5. Neutral
6. Min/max sensor.
7. 0-10V DC out
8. Neutral
9. 0 - 10V DC in
IMPORTANT: Read these
instructions before installation and
!
wiring of the product.
2 3 4 5 6 7 8 9
1
1 1 L1
L2
L3
L3 L2
3 L1
Fig 1
TG-R5xx
1 2
3 4
TG-R6xx
Fig 2
1
2
1 2
3 4
TG-R4xx
Fig 3
1
3
Box 116 428 22 KÅLLERED SWEDEN
Tel +46 (0)31 720 02 00
Fax +46 (0)31 720 02 50
INSTRUCTIONS
200
Triac controller for proportional control
of electric heating
TTC25 is a proportional controller for electric heating with automatic voltage
adaption. TTC25 pulses the whole load On - Off. The ratio between On-time
and Off-time is varied 0 - 100% to suit the prevailing heat demand. The
current is always switched at zero phase angle to prevent RFI.
TTC25 can control both symmetrical Y-connected 3-phase heaters and
symmetrical or asymmetrical Delta-connected heaters.
TTC25 is only intended for electric heating control. The control principle
makes it unsuitable for motor- or lighting control.
TTC25 is intended for DIN-rail mounting.
Mount TTC25 on a DIN-rail in a cabinet or other enclosure.
Mount TTC25 vertically with the text right side up.
Protection class:
IP20.
Ambien temperature:
0 - 40°C
N.B. TTC25 emits approx. 45W of heat at full output which must be
dissipated.
Supply voltage (fig 1)
Terminals L1in, L2in and L3in.
Supply voltage: 210-255 or 380-415V AC
3 phase, 50 - 60 Hz with automatic voltage adaption.
Maximum current 25A/phase.
N.B. The supply voltage to TTC25 should be wired via an all-pole switch
with a minimum contact gap of 3mm.
N.B. TTC25 must be earthed.
Load (fig 1)
Terminals L1out, L2out and L3out.
Resistive 3-phase heater without neutral.
Maximum load:
3300W/phase at 230V phase - phase voltage (25A).
5750W/phase at 400V phase - phase voltage (25A).
Minimum load:
530W/phase at 230V phase - phase voltage (4A).
920W/phase at 400V phase - phase voltage (4A).

Installation

Wiring
INSTRUCTIONS
Main sensor and external setpoint (figs 2-6)
Terminals 1 and 4. Low voltage. Not polarity sensitive.
N.B. Terminals 2 and 3 are internally connected and are used
to simplify wiring when using external setpoint.
N.B. Choice of internal or external setpoint is made using
switch 1.
Limiting sensor (fig 7)
Terminals 5 and 6. Low voltage. Not polarity sensitive.
When running room temperature control the supply air temperature can
be limited to a maximum and/or a minimum. The limiting sensor is placed
in the supply air duct after the heater.
Choice of function is made using switches 2 and 3. Choice of limiting
temperatures is made on potentiometers Min and Max.
N.B. As limiting sensor TG-K360 must be used.
Figures
Fig 1: Wiring of supply voltage and heater.
Fig 2: Wiring of room sensor TG-R530 or
TG-R6xx when using internal setpoint.
Fig 3: Wiring of room sensor TG-R430 used as external setpoint and
sensor.
Fig 4: Wiring of floor or duct sensor when using internal setpoint.
Fig 5: Wiring of external separate sensor when using TG-R4xx as
external setpoint.
Fig 6: Wiring of external, separate sensor when using potentiometer
TBI-xx as external setpoint.
Fig 7: Wiring of limiting sensor.
N.B. TG-K360 must be used.
Settings
Potentiometers
Setp. Setpoint 0 - 30°C.
Min
Minimum limit for supply air temperature when running room
temperature control.
Max
Maximum limit for supply air temperature when running room
temperature control.
CT
Cycle time. 6 - 60 seconds.
Switches
1
Down = External setpoint in use.
Up = Internal setpoint in use.
2
Down = Minimum limit not active.
Up = Minimum limit active.
3
Down = Maximum limit not active.
Up = Maximum limit active.
N.B.
Minimum and maximum limiting functions may be used
separately or at the same time.