1. Drill two 3.2 mm (1/8 inch) holes for the mounting box
with 100 mm distance into the transom.
Drill a 14 mm (0.55 inch) hole into the transom for the
sensor cable (Figure 7).
Notice:
For convenient installation use the supplied drilling
template.
Transom
*
IMPORTANT for correct mounting:
=
This center line is the center of the door
Figure 7:
Drilling template
2. Disconnect the cable from the IMS 100 Pro sensor.
WARNING: Avoid pollution or contamination when the
plug is disconnected. If the connector is removed and
dust entered warranty is lost.
3. Route the cable up from the top through the 14 mm
hole (0.55 inch) in the transom to the door opening.
4. Mount the mounting box with the two 3.5 mm self-
tapping screws on the transom.
5. Connect the connector to the IMS 100 Pro housing.
6. Slide the preassembled sensor into the mounting box
and fix it with two expanding rivets.
7. Remove the foil from the optical cover after the
electrical connection but before testing.

5.3.2 Flush mounting

Figure 8:
Flush mounting (center opening doors)
The sensor has to be installed into the transom:
Distance:
≥ 18 mm ≤ 100 mm
Figure 9:
Position of the rectangle in the transom (center
opening doors)
6
*
100
12
Hall side
Preassembled sensor
Expanding rivets
Position of rectangle
Transom
1. Cut a rectangle of 30 x 89 mm out of the transom.
2. Drill two 4.8 mm (3/16 inch) diameter holes to mount
the preassembled sensor into the transom with 120
mm distance from drilling hole to drilling hole (Figure
10).
Notice:
For a convenient installation use the supplied
template.
Transom
Hall side
*
=
IMPORTANT for correct mounting:
This center line is the center of the door
Figure 10:
Template (Drilling and cutting out)
3. Route cable up through the hole in the transom. Slide
the preassembled sensor into the cutout and fix it with
the two expanding rivets.
4. Remove the foil from the optical cover after the
electrical connection but before testing.
5.4

Right side-opening doors

NOTICE
The further away the IMS 100 Pro is mounted
from the doorframe, the earlier the sensor
switches into the door mode (door has been
detected) and no longer detects objects.

5.4.1 Surface mounting

Figure 11:
Surface mounting (right side-opening doors)
*
89
120
Mounting box
Self tapping screws
Preassembled sensor
Expanding rivets