The water quality must be in accordance with the
specifications listed the table below:
Items to be controlled
pH
at 25°C
Electrical
conductivity
[mS/m] at
25°C
Chloride Ion
[mg Cl˜/l]
Sulfate Ion
[mg SO
²˜/l]
4
M-alcalinity
(pH4.8)
[mg CaCO
/l]
3
Total hardness
[mg CaCO
/l]
3
Calcium
hardness
[mg CaCO
/l]
3
Silica Ion
[mg SiO
/l]
2
Items to be referred to
Iron
[mg Fe/l]
Copper
[mg Cu/l]
Sulfide Ion
[mg S²˜/l]
Ammonium
Ion
[mg NH
+/l]
4
Remaining
chloride
[mg Cl/l]
Free carbide
[mg CO
/l]
2
Stability index
The water pressure should not exceed the maximum
working pressure of 10 bar.
NOTE
make sure that the water pressure will never
exceed the maximum allowable working

PIPING INSULATION

The complete water circuit, inclusive all piping, must be
insulated to prevent condensation and reduction of the cooling
capacity.
Protect the water piping against water freezing during winter
period (e.g. by using a glycol solution or heatertape).
Downloaded from
www.Manualslib.com
volume of every individual chiller in the system.
Circulating
Supply
water
water
6.8~8.0
6.8~8.0
<40
<30
<50
<50
<50
<50
<50
<50
<70
<70
<50
<50
<30
<30
<1,0
<0,3
<1,0
<0,1
not
not
detectable
detectable
<1,0
<0,1
<0,3
<0,3
<4,0
<4,0
-
-
Provide adequate safeguards in the water circuit to
pressure.
manuals search engine
DISCHARGE FROM PRESSURE RELIEF DEVICES
Discharge of the refrigerant into installation area has to be in
accordance with local regulations. If required it is possible to
connect a 1" pipe to each pressure relef valve on the
condenser and ½" pipe to each pressure relief valve on the
Tendency
evaporator.
if out of
Cross section and length of the discharge line must comply
criteria
with local codes.
corrosion+

FIELD WIRING

scale
corrosion+
scale
All field wiring and components must be installed by a
licensed electrician and must compy with relevant
European and national regulations
corrosion
.
The field wiring must be carried out in accordance with
the wiring diagram supplied with the unit and the
corrosion
instructions given below.
scale
Be sure to use a dedicated power circuit. Never use a
power supply shared by another appliance.
scale
NOTE Verify on the wiring diagram all electrical actions
mentioned below, in order to understand the operation
of the unit more deeply.
scale

Parts table

scale
F1,2..........................Main fuses for the unit
L1, 2, 3......................Main supply terminals
PE........................... Main earth terminal
corrosion+
S6S..........................Setpoint override
scale
FS........................... Flowswitch
Q10..........................Main isolator switch
corrosion
---.............................Field wiring
corrosion

Power circuit and cable requirements

corrosion
1
The electrical power supply to the unit should be
arranged so that it can be switched on or off
independently of the electrical supply to other
corrosion
items of the plant and equipment in general.
2
A power circuit must be provided for connection of
corrosion
the unit. This circuit must be protected with the
required safety devices, i.e. a circuit breaker, a
corrosion+
slow blow fuse on each phase and an earth leak
scale
detector. Recommended fuses are mentioned on
the wiring diagram supplied with the unit.
Switch off the main isolator switvch before making any
connections (switch off the circuit breaker, remove or
switch off the fuses).
Connection of the watercooled water chiller power
supply
1
Using the appropriate cable, connect the power
circuit to the L1, L2 and L3 terminals of the unit.
2
Connect the earth conductor (yellow/green) to the
earthing terminal PE.
D-EIMWC01004-14EU - 8/190