Technische Daten
Versorgungsspannung
RCM410R-1:
Versorgungsspannung U
........................................................ DC 24 V
s
Toleranz von U
..............................................................-30...+25 %
s
Eigenverbrauch ......................................................................... ≤ 2 W
RCM410R-2:
Versorgungsspannung U
................AC/DC 100...240 V (47...63 Hz)
s
Toleranz von U
........................................................................ ±15 %
s
Eigenverbrauch ....................................................... ≤ 2 W / ≤ 3,5 VA
Messkreis
Messstromwandlertyp ....................... CTAC..., W..., WR..., WS...
Bürde ...........................................................................................33 Ω
Ansprech-Charakteristik ..............................................................Typ A
Bemessungsspannung U
...........siehe Datenblatt Messstromwandler
n
Frequenzbereich ............................................................... 42...70 Hz
Messbereich RMS ............................................................2 mA...50 A
Ansprechdifferenzstrom I
...........................................10 mA...30 A
Δn
Betriebsmessabweichung ...........................±10 % (bei 0,5...5 x I
Prozentuale Ansprechunsicherheit ................................... 0...–20 %
Kontaktdaten nach IEC 60947-5-1:
Gebrauchskategorie ............... AC 13 AC 14 DC-12 DC-12 DC-12
Bem.betriebsspannung .......... 230 V 230 V 24 V 110 V 220 V
Bem.betriebsstrom .................. 5 A
Min. Kontaktbelastbarkeit ...........................1 mA bei AC/DC ≥ 10 V *
* bezieht sich auf Relais, die noch nicht mit hohen Kontaktströmen be-
trieben wurden
Anschluss
Anschlussart ............................................................................ Push-In
Anschlussvermögen
starr .................................................. 0,2...1,5 mm² (AWG 24...16)
flexibel .............................................. 0,2...1,5 mm² (AWG 24...16)
mit Aderendhülse ...................................................0,25...0,75 mm²
mit Aderendhülse .....................................................1,0...1,5 mm² *
* nur Crimpzange (ähnlich CRIMPFOX 6 / Weidmüller PZ6/PZ6/5)
verwenden.
Alle Rechte vorbehalten.
Nachdruck und Vervielfältigung
nur mit Genehmigung des Herausgebers.
Bender GmbH & Co. KG
Postfach 1161 • 35301 Grünberg • Deutschland
Londorfer Str. 65 • 35305 Grünberg • Deutschland
Tel.: +49 6401 807-0 • Fax: +49 6401 807-259
E-Mail: info@bender.de • www.bender.de
Δn
3 A
1 A
0,2 A 0,1 A
Technical data
Supply voltage
RCM410R-1
Supply voltage U
.................................................................... DC 24 V
s
Tolerance U
...................................................................-30...+25 %
s
Power consumption .................................................................. ≤ 2 W
RCM410R-2
Supply voltage U
............................AC/DC 100...240 V (47...63 Hz)
s
Tolerance U
............................................................................. ±15 %
s
Power consumption .................................................≤ 2 W / ≤ 3.5 VA
Measuring circuit
Measuring current transf. type .......... CTAC..., W..., WR..., WS...
Load .............................................................................................33 Ω
Operating characteristics ..........................................................Type A
Rated voltage U
..........see datasheet measuring current transformer
n
Frequency range ..............................................................42...70 Hz)
Measuring range RMS .....................................................2 mA...50 A
Residual operating current I
)
Operating uncertainty ...................................±10 % (at 0.5...5 x I
Relative uncertainty .......................................................... 0...–20 %
Contact data acc. to IEC 60947-5-1:
Utilisation category ................ AC 13 AC 14 DC-12 DC-12 DC-12
Rated op. voltage ................... 230 V 230 V 24 V 110 V 220 V
Rated op. current. .................... 5 A
Minimum contact rating ................................1 mA at AC/DC ≥ 10 V *
* refers to relays that have not been operated with high contact cur-
rents.
Connection
Connection type ...................................................................... push-in
Connection properties
rigid ................................................... 0.2...1.5 mm² (AWG 24...16)
flexible .............................................. 0.2...1.5 mm² (AWG 24...16)
with ferrule .............................................................0.25...0.75 mm²
with ferrule ..............................................................1.0...1.5 mm² *
*Use crimping pliers only (simliar CRIMPFOX 6 / Weidmüller PZ6/
PZ6/5).
Londorfer Str. 65 • 35305 Grünberg • Germany
......................................10 mA...30 A
Δn
3 A
1 A
All rights reserved.
Reprinting and duplicating
only with permission of the publisher.
Bender GmbH & Co. KG
PO Box 1161 • 35301 Grünberg • Germany
Tel.: +49 6401 807-0 • Fax: +49 6401 807-259
E-Mail: info@bender.de • www.bender.de
)