Siemens SITRANS P310 Kompaktbetriebsanleitung Seite 36

Mit hart
Vorschau ausblenden Andere Handbücher für SITRANS P310:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 83
Differential pressure and flow rate input
Lower measuring limit
Measuring cell with silicone oil filling -100 % of max. measuring range
Upper measuring limit
Start of scale value
7.2
Output
Output
Output signal
Low saturation limit (fully adjustable)
High saturation limit (fully adjustable)
Ripple (without HART communication)
adjustable time constants damping coefficient
Adjustable time constants (T63) with local operation
Current transmitter
Failure signal
Load
Without HART communication
With HART communication
HART communicator (Handheld)
SIMATIC PDM
Characteristic curve
SITRANS P310 with HART
A5E35075329-01, 05/2015
6 ... 600 mbar
0.6 ... 60 kPa
2.409 ... 240.9 inH
O
2
0.016 ... 1.6 bar
1.6 ... 160 kPa
6.424 ... 642.4 inH
O
2
0.05 ... 5 bar
5 ... 500 kPa
20.08 ... 2008 inH
O
2
0.3 ... 30 bar
30 ... 3000 kPa
4.35 ... 435 psi
(-33 % for measuring cell 30 bar/3000 kPa/435 psi) or
30 mbar a/3 kPa a/0.44 psi a)
100% of maximum span
Between the measuring limits (fully adjustable)
HART
4 ... 20 mA
3.55 mA, set to 3.84 mA in the factory
23 mA, set to 20.5 mA or optionally 22.0 mA in the factory
I
≤ 0.5 % of the max. output current
SS
0 ... 100 s, continuously adjustable
0 ... 100 s, in steps of 0.1 s
Factory-set to 2 s
3.55 ... 23 mA
3.55 ... 23 mA
Resistor R [Ω]
U
H
R =230 ... 1100 Ω
R =230 ... 500 Ω
Power supply in V
Linearly increasing or linearly decreasing
Linear increase or decrease or root extraction increase
(only for P310 differential pressure and flow rate)
35