DIMENSIONS
1 2 3 4 5 6 7
68
97
unit
enable
bypass
fan
setpoint
override
dial
104
Fig. 5. CLCM1H,6H,6T dimensions in mm
CONFIGURATION (CLCM6H,6T)
After installation, the CLCM6H,6T must be configured in order
to perform as desired. This is done by using the buttons and
the setpoint dial.
Normal Operating Mode
After the CLCM6H,6T is powered up, it will display the room
temperature and will operate as configured by default. After
power-up, all display segments go ON for approx. one second
(see Fig. 6).
AUTO
MANU
PROG
Fig. 6. Display of all segments after power-up
Entering Configuration Mode
1. Press FAN OVERRIDE for min. 5 sec.
2. Press UNIT ENABLE, then release FAN OVERRIDE,
continue holding UNIT ENABLE for min. 5 sec.
3. Release UNIT ENABLE.
RESULT: The display shows
configuration (see below).
4. Press and hold FAN OVERRIDE while turning the
setpoint dial to select the parameter number.
CLCM1H,6H,6T DIGITAL WALL MODULES – INSTALLATION INSTRUCTIONS
28
33
and the DWM is ready for
RESULT: The parameters with their currently set values are
displayed; the ≡ behind the value indicates the
currently set value (see below for values).
5. Release FAN OVERRIDE and turn the setpoint dial to
select the parameter value.
6. Confirm selection by pressing UNIT ENABLE.
7. Repeat steps 4 to 6 to configure next parameter, or
press BYPASS to leave the configuration mode.
NOTE:
After approx. 10 sec without further action, the DWM
automatically reverts to normal mode.
P1
Setpoint type setting / Scale type setting
Fahrenheit relative
Fahrenheit absolute
*
Celsius relative (default)
Celsius absolute
P2
Room temperature display
Do not display room temperature
(setpoint, only)
*
Display room temperature (default)
Display room temperature and humidity, alternating
every 5 seconds (CLCM6H212, only)
P3
Bargraph use setting
No Fan
Auto, OFF, ON
Auto, OFF, 2 Speeds
*
Auto, OFF, 3 Speeds (default)
P4
Controller type setting
*
LCD signaling (default)
P5
Pin 4 (bypass/fan) grounding
Pin 4 not shorted to GND if override is pressed
*
Pin 4 shorted to GND if override is pressed (default)
P6
Device type
This item configures different devices.
IMPORTANT:
Stay on P6:1 and do not change!
P7
Temperature setpoint offset
*
Temperature offset; values of 0 through 99 are valid.
50 = no change, 49 = -0.1 °C, 51 = +0.1 °C, etc. This offset
varies the LCD display value, only. In order for this offset to
have the proper effect, it must be set in the controller, too.
P8
Remote reset of temperature setpoint overrides and
fan speed overrides
*
disable remote reset of temperature setpoint override
and disable remote reset of fan speed override.
enable remote reset of temperature setpoint override
and disable remote reset of fan speed override
(takes effect ONLY if
selected AND
disable remote reset of temperature setpoint override
and enable remote reset of fan speed override (takes
effect ONLY if
enable remote reset of temperature setpoint override
and enable remote reset of fan speed override (takes
effect ONLY if
has been selected)
IMPORTANT
In addition to P8, parameters P1 and P4 must also be set
accordingly for the wall module – see above!
3
or
has been
has been selected)
has been selected)
or
has been selected AND
MU1Z-0902GE51 R0214B