Herunterladen Inhalt Inhalt Diese Seite drucken

Diagnostic Self-Check List (U-10Mes2E8); Alarm Display - Panasonic U-20GES3E5 Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für U-20GES3E5:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 49

16. Diagnostic Self-Check List (U-10MES2E8)

How to know LEDs 1 and 2 alarm display on outdoor unit control board
LED 1
LED 2

Alarm display

Alternating
After LED1 blinks M times, LED2 blinks N times.
This will be repeated.
For example: After LED1 blinks twice, LED2 blinks 17 times. This will be repeated.
(
: Blink)
Connect the outdoor unit maintenance remote controller to the RC plug (3P, BLU) on outdoor unit control board
and make confirmation.
Table 8
Remote control display
E06
Outdoor unit receiving failure from indoor unit
E12
Prohibit starting auto address setting
E15
Auto address alarm (A small number of indoor units)
E16
Auto address alarm (A large number of indoor units)
E20
No indoor unit during auto address setting
E21
Receiving failure of main system from sub system when link wiring is used for outdoor units
E22
Receiving failure of sub system from main system when link wiring is used for outdoor units
E24
Receiving failure of relay control unit from outdoor unit(s)
E25
Failure of outdoor unit address setting (Duplicative)
E26
Inconsistencies in number of outdoor units
E29
Failure of outdoor unit to receive relay control unit
E30
Failure of transferring outdoor unit serial
E31
Wiring error between the P.C. board ( [L-Pow], [HIC] wire)
F04
Compressor 1 discharge temperature sensor abnormal
F05
Compressor 2 discharge temperature sensor abnormal
F06
Outdoor unit heat exchanger 1 gas (inlet) temperature sensor abnormal
F07
Outdoor unit heat exchanger 1 liquid (outlet) temperature sensor abnormal
F08
Outdoor temperature sensor abnormal
F12
Compressor inlet temperature sensor abnormal
F14
Supercooling gas temperature sensor abnormal
F16
High pressure sensor abnormal, high-load
F17
Low pressure sensor abnormal
F23
Outdoor unit heat exchanger 2 gas (inlet) temperature sensor abnormal
F24
Outdoor unit heat exchanger 2 liquid (outlet) temperature sensor abnormal
F31
Outdoor unit nonvolatile memory (EEPROM) error
H01
Compressor 1 abnormal current values (Overcurrent)
H03
Compressor 1 CT sensor disconnected, short-circuit
H05
Compressor 1 discharge temperature sensor disconnected
H06
Low pressure abnormal lowering
H07
Oil loss - error
H08
Oil sensor (connection) error 1
Contents of Alarm Display
Number of blinks
Type of alarm
2
3
M
4
5
6
The alarm shows "P17".
EN - 20
Alarm P
Alarm H
N = number of alarm No.
Alarm E
Alarm F
Alarm L
Alarm contents
[DISCH1]
[DISCH2]
[EXG1]
[EXL1]
[TO]
[SCT]
[SCG]
[HPS]
[LPS]
[EXG2]
[EXL2]

Werbung

Inhaltsverzeichnis
loading