15. CHECK OF DENSITY LIMIT

The refrigerant (R32), which is used in the air conditioner, is a flammable refrigerant. So the requirements for installation space of
appliance are determined according to the refrigerant charge amount [m
The minimum indoor floor space compared with the amount of refrigerant is roughly as follows:
20.0
18.0
16.0
14.0
12.0
10.0
8.0
6.0
4.0
2.0
0.0
0
[m
]
: The refrigerant charge amount (Total of refrigerant at shipment and refrigerant charge amount in the field).
c
[m
] : Maximum refrigerant charge amount
max
U-36PZH2E5
U-50PZH2E5
[m
]
max
] ≤ 1.22
[m
: Can be installed
c
] ≤ [m
1.22 < [m
] : Installation possible with in the range of slanted line part
c
max
[m
] > [m
]
: Can not be installed
max
c
Can be installed
0.5
1
1.5
2
[m
1.22
1.35
1.80
U-60PZH2E5
U-60PZ2E5
U-71PZ2E5
1.35
1.80
] used in the appliance.
c
U-36PZH2E5, U-50PZH2E5
Can not be installed.
Can not be installed
2.5
3
3.5
] : the refrigerant
c
charge amount (kg)
3.50
U-100PZ2E5
U-100PZ2E8
3.50
31
* U-36PZH2E5, U-50PZH2E5,
U-60PZH2E5, U-60PZ2E5
U-71PZ2E5, U-100PZ2E5,
U-100PZ2E8
Can not be installed.
* U-36PZH2E5, U-50PZH2E5,
U-60PZH2E5, U-60PZ2E5,
U-71PZ2E5
Can not be installed.
4
4.5
5
3.88
U-125PZ2E5
U-140PZ2E5
U-125PZ2E8
U-140PZ2E8
3.88
3.88