BACnet IP configuration
This web page is used to configure some of the parameters relevant to the BACnet IP protocol standard.
Apart from these
settings,
configured in the Network Settings menu.
Fig. 5
Real Time Ethernet Protocol Configuration - BACnet IP
Object
Description
Select UDP Port Number. The default number is 47808,the IANA-assigned standard UDP
UDP Port Number
port number for BACnet IP.
Select Device Instance. The default number is 22700. The Device Instance must be unique in
Device Instance
the BACnet network. For Grundfos, the number is 227 and it is fixed. The last three digits can
be changed.
Device Name
You can name the device. The device name must be unique in the BACnet network. Optional.
Device Location
You can name the device location for local identification. Optional.
Select the maximum Application Protocol Data Unit, between 50 and 1476. The default value
Max APDU
is 1476 bytes.
If enabled and BACnet communication stops, the watchdog timer restarts the internal network
Network Watchdog
module if it times out.
Timer
You can configure time-out from 2 minutes to 1440 minutes in steps of 1 minute.
A value of 1 is illegal and a value of 0 disables the watchdog.
Custom device
If ticked, CIM 500 is configured to use a BACnet custom device instance number.
instance enable
Foreign Device
If ticked, CIM 500 is configured as a foreign device.
IP Address
Enter the foreign IP address.
UDP Port
Select the foreign UDP port number. The default number is 47808.
Select the time period in seconds during which the foreign device must re-register on the
Re-Register Time
BACnet network.
If enabled and BACnet communication stops, the watchdog timer restarts the internal network
Network Watchdog
module if it times out.
Timer
You can configure time-out from 2 minutes to 1440 minutes in steps of 1 minute.
A value of 1 is illegal and a value of 0 disables the watchdog.
188
BACnet IP will use the IP address, subnet mask, default gateway and DHCP setting