6. Fault finding

6.1 PROFINET IO

You can detect faults in a module by observing the
status of the two status LEDs. See the tables below.
CIM 500 fitted in a Grundfos product or CIM 500
fitted in a CIU 500
Ensure that SW1 is in position "0" to select
PROFINET.
Fault (LED status)
1.
Both LEDs remain off when
the power supply is
connected.
2.
LED1 remains off.
3.
LED2 is flashing red.
4.
LED2 is permanently red.
5.
LED1 is permanently red.
6.
LED1 is flashing red, 3 Hz.
7.
LED1 is pulsing red, 0.3 Hz.
8.
LED1 is permanently red
and green at the same time.
9.
LED2 is permanently red
and green at the same time.
12
Possible cause
a)
The module is fitted
incorrectly in the Grundfos
product.
b)
The module is defective.
c)
CIU 500 is defective.
a)
SW1 is not set correctly.
a)
No internal communication
between the module and the
Grundfos product.
b)
No internal communication
between CIU 500 and the
Grundfos product.
a)
The module does not support
the connected Grundfos
product.
a)
The module does not support
the connected Grundfos
product.
b)
SW1 is in illegal position.
a)
Fault in the PROFINET IO
configuration of the module.
a)
The connection to the master
is lost.
a)
Error in firmware download.
a)
Memory fault.
Remedy
Check that the module is fitted and
connected correctly.
Replace the module.
Replace CIU 500.
Set the switch to "0".
Check that the module is fitted
correctly in the Grundfos product.
• Check the cable connection
between the Grundfos product
and CIU 500.
• Check that the individual
conductors have been
connected correctly, for
example not reversed.
• Check the power supply to the
Grundfos product.
Contact the nearest Grundfos
company.
Contact the nearest Grundfos
company.
Set the switch to "0".
• Restart CIM 500. Use the
RESTART button on the
webserver, or power cycle the
product. See section
PROFINET IO
configuration.
• Check that the PROFINET IO
IP address configuration is
correct. Check the device name
in CIM 500 and PROFINET IO
master.
• Check that the right GSDML file
is used.
• Check the cables.
• Check that the master is
running.
Use the webserver to download
the firmware again. See section
Update
in the appendix.
Replace the module.