Herunterladen Inhalt Inhalt Diese Seite drucken

Grundfos CIM 500 Installations- Und Bedienungsanleitung Seite 186

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 19
PROFINET IO configuration
This web page is used to configure all the parameters relevant to the PROFINET IO protocol standard.
Fig. 3
RealTime Ethernet Protocol Configuration - PROFINET IO
Object
Description
Fill in a device name according to the PROFINET rules:
• It consists of one or more labels separated by a dot.
• The total length is 1 to 240 characters.
Device Name
• The length of a label is 1 to 63 characters.
• Labels only consist of lower case characters, digits and "-".
The first and the last character of a label must not be "-".
This field is read only. The IP address is assigned from the PLC. PROFINET IO is not
IP Address
allowed to share the IP address with a CIM 500 webserver.
Subnet Mask
This field is read only. The subnet mask is assigned from the PLC.
Gateway
This field is read only. The gateway address is assigned from the PLC.
The module can be put in product simulation mode to generate realistic simulated
values of all the PROFINET IO input data. It will thus be possible to connect a
PROFINET IO master to a module fitted in a CIU or an E-box without installing this
device in a real industrial process system. In an office environment, it can then be
Grundfos product
verified that communication works, and data is received and handled correctly by the
simulation
PROFINET IO master application program (for example PLC program) before installing
the device.
To enable product simulation, select a product type from the dropdown list.
To terminate product simulation, select "No Simulation".
Press the restart button if the LED1 flashes red, which indicates a wrong or missing
Restart
PROFINET IO configuration.
186

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis