BEHA UNITEST TELARIS 0100 Bedienungsanleitung Seite 51

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Loop Impedance Z
:
L
Measurement Range:
Resolution:
Tolerance:
Test current:
Load time:
Mains nominal voltage:
Measurement time:
Max. nominal voltage fluctation during the measurement: 1%
Protective conductor must not be live.
Automatic measurement range selection
Prospective Short-Circuit Current :
Measurement Range:
Resolution:
Short-circuit current is calculated
Low Ω Measurement:
Measurement Range:
Resolution:
Tolerance:
output voltage (with no load) Uq: 5 ... 9V dc
Test Current:
Measurement Time:
Number of Measurements:
Compensated test lead resistance: max. 1,99Ω
RCD-Test:
Nominal Voltage:
Measurement time:
Protective conductor must not be live
Measurement of Contact Voltage UB:
Measurement current:
Measurement duration:
Measurement Range:
Resolution:
Tolerance:
Threshold values:
Contact voltage is measured at 1/3 I∆N and may be extrapolated to nominal current I∆N or double nominal
current 2 I∆N for time delayed residual current circuit breakers.
0,05 ... 19,99Ω, 20,0 ... 199,9Ω, 200 ... 1999Ω
0,01Ω, 0,1Ω, 1Ω
±(6% rdg. +5 Digit)
< 8A
< 80 ms
230V, 50...60Hz, cosϕ 0,95
ca. 3s
0,10...9,99A, 10,0...99,9A, 100...999A,
1,00...9,99kA, 10,0...23,0kA
0,01A, 0,1A, 1A, 0,01kA, 0,1kA
0,05 ... 19,99Ω
0,01Ω
±(3% rdg. +5 Digit)
200mA (at resistance < 2Ω+Rcomp)
1s
1600 (1Ω, 1 Measurement - 25s break)
230V, 50...60Hz
1s (Pre-Test, Mains-Test)
ca. 31s (Mains-Test time delayed RCD)
max. 18s
1/3 nominal fault current I∆N
200ms, when exeeding limits immediate measurement
1...63 V
1 V
-0%...+10%, +5 Digit
UL selection between 25V / 50V
Technical Data
51