❚ Emergency stop

(The operations depend on the jumper line setting. For more information on jumper line settings, consult
your dealer.)
When the
is fl ashing, an emergency stop signal is being input by the external contact.
All the units being managed by this central control are stopped and the CENTER / REMOTE setting becomes
. In this state, operation from remote controllers is impossible.
During emergency stop input, RUN and CENTER / REMOTE operations from this central control are not pos-
sible.
If the external contact is cancelled, at that point in time, the units have stopped. (The
stop fl ashing and
return to being lit up.)
However, even if the contact is cancelled within 2 minutes of being input, the display remains the same as for
emergency stop input for 2 minutes.
Note that after the contact is cancelled, the CENTER / REMOTE setting returns to its original status, but the
units do not run until you execute a RUN command.