Herunterladen Inhalt Inhalt Diese Seite drucken

Center / Remote Setting - Mitsubishi Heavy Industries SC-SL2NA-E Anwenderhandbuch

Zentralsteuerung
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 80

CENTER / REMOTE Setting

Set whether to manage the indoor units being managed centrally using the central control or locally using the
remote controller that comes with each indoor unit.
❚ Setting contents and enabled / disabled button operations
Setting contents
CENTER
CENTER and REMOTE
• Setting
1. Press the ALL / GROUP / ONE button and select either
The options are displayed in the order.
Select all indoor units, a group of indoor units, or one indoor unit to be run or stopped.
2. Press the SELECT (
If ALL is selected in Operation 1, skip Operation 2.
To select all the groups, select "88".
3. Press the CENTER/REMOTE button and select
The options are displayed in the order.
The displayed operations subject is set.
Note
When multiple central controls are connected within the same indoor unit, set this setting (CENTER / REMOTE)
the same on all of them.
If the switching jumper line J1 is cut, the CENTER / REMOTE button is disabled.
For more information on jumper line settings, consult your dealer.
This setting can not be made during DEMAND or emergency stop input.
Operation is only possible from the central control. Operation with an
indoor unit's remote controller is not possible.
Operation is possible from the central control and from an indoor unit's
remote controllers. The last one pushed takes precedence.
Operation from the central control is not possible. Operate from an indoor
REMOTE
unit's remote controller.
1
2
or
) button to set the group number or unit number.
Enabled / disabled button operations
3
,
,
, or
– 13 –
, or
.
.

Quicklinks ausblenden: