Installation site selection - Indoor unit
AVOID
• Direct sunlight.
• Nearby heat sources that may affect unit performance.
• Areas where leakage of flammable gas may be expected.
• Locations where large amounts of oil mist may occur (such as
in kitchen or near factory equipment) because oil contamination
can cause operation problems and may deform plastic surfaces
and parts of the unit.
• Unsteady locations that will cause noise or possible water
leakage.
• Locations where the remote control unit will be splashed with
water or affected by dampness or humidity.
• To make holes in areas where electrical wiring or conduits are
located.
DO
• Select an appropriate position from which every corner of the
room can be uniformily cooled.
ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED)
Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system; it has to be insulated with foamed polyethylene
(min. thickness 8mm).
MODEL
MCAV 18X
MCAV 22X
PVC pipe for condensate drain pipe (ø int.18mm) in length suitable to let the condensate flow into the outside drainage.
Anti-freeze oil for flare connections (about 30g).
Electric wire: use insulated copper wires of size and length as shown at paragraph "SYSTEM WIRING DIAGRAMS".

ELECTRICAL DATA

Power supply wiring length
MODEL
Cross section area (mm
2
)
GR/GRV 18X
C16X - C18X
GR/GRV 22X
* 3-phase version
TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS
TUBING LENGTH AT
MODEL
MCAV 18X
MCAV 22X
* If total tubing length becomes 7,5 to 20m; 7,5 to 30m (max.), charge additional 25 g/m refrigerant.
No additional charge of compressor oil is necessary.
NARROW TUBE
OUTER DIAMETER
6,35 mm
6,35 mm
LENGTH, SIZE WIRES AND DELAYED FUSE
("A") m
2,5
22
100*
16
87*
H
MAX. ALLOWABLE
LIMIT OF TUBING
SHIPMENT
(m)
7,5
7,5
• Select a sufficiently strong location to support the weight of the
unit.
• Select a location where tubing and drain hose have the shortest
run to the outside.
• Allow access for operation and maintenance as well as
unrestricted air flow around the unit.
Installation site selection - Outdoor unit
AVOID
• Heat sources, exhaust fans.
• Direct sunlight.
• Damp, humid or uneven locations.
• To make holes in areas where electrical wiring or conduits are
located.
DO
• Choose places as cool as possible and well ventilated.
• use lug bolts or equal to bolt down the unit, reducing vibration
and noise.
MIN. THICKNESS
OUTER DIAMETER
0,8 mm
0,8 mm
Power line length
("B") m
2,5
20 m
30 m
LIMIT OF ELEVATION
LENGTH
DIFFERENCE
(m)
20
30
3
LARGE TUBE
MIN. THICKNESS
12,7 mm
15,88 mm
Control line length
Delayed fuse
("C") m
1
20 m
30 m
H
REQUIRED AMOUNT OF
ADDITIOONAL
H
REFRIGERANT
(m)
(g / m)*
7
7
EG
0,8 mm
1 mm
20A
10A
20A
10A
25
25
(go on page 4)