Herunterladen Diese Seite drucken

Werbung

Installation site selection - Indoor unit
AVOID
• Direct sunlight.
• Nearby heat sources that may affect unit performance.
• Areas where leakage of flammable gas may be expected.
• Locations where large amounts of oil mist may occur (such as in
kitchen or near factory equipment) because oil contamination can
cause operation problems and may deform plastic surfaces and
parts of the unit.
• Unsteady locations that will cause noise or possible water leakage.
EG
• Locations where the remote control unit will be splashed with water
or affected by dampness or humidity.
• To make holes in areas where electrical wiring or conduits are
located.
• To place appliances under tension (household appliances,
computers), because in case of emergency operation the unit could
drip condensate water.
DO
• Select an appropriate position from which every corner of the room
ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED)
G
Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system; it has to be insulated with foamed polyethylene
(min. thickness 8mm).
MODEL
CAF94/124
CAF185
G
PVC pipe for condensate drain pipe (ø int.18mm) in lenght suitable to let the condensate flow into the outside drainage.
G
Anti-freeze oil for flare connections (about 30g.).
G
Electric wire: use insulated copper wires of size and length as shown in the table "ELECTRICAL DATA" and at paragraph "SYSTEM WIRING
DIAGRAMS".

ELECTRICAL DATA

MODEL
GRF94/95
GRF124/125
GRF185
Cross section area (mm2)
* 3-phase version
TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS
MODEL
CAF94
CAF124
CAF185
* For every meter of tube more than standard lenght at shipment, add refrigerant as shown in the table. No additional charge
of compressor oil is necessary.
NARROW TUBE
OUTER DIAMETER
6,35 mm
6,35 mm
LENGTH, SIZE WIRES AND DELAYED FUSE
Power supply wiring length
(A-B) m
50
35
30
150*
2,5
MAX. ALLOWABLE
TUBING LENGTH AT
SHIPMENT
(m)
7,5
7,5
10
can be uniformily cooled.
• Select a sufficiently strong ceiling to support the weight of the unit.
• Select a location where tubing and drain hose have the shortest run
to the outside.
• Allow access for operation and maintenance as well as unrestricted
air flow around the unit.
Installation site selection - Outdoor unit
AVOID
• Heat sources, exhaust fans.
• Direct sunlight.
• Damp, humid or uneven locations.
• To make holes in areas where electrical wiring or conduits are
located.
DO
• Choose places as cool as possible and well ventilated.
• use lug bolts or equal to bolt down the unit, reducing vibration and
noise.
MIN. THICKNESS
0,8 mm
0,8 mm
Power line length
(C) m
15
15
25
2,5
LIMIT OF TUBING
LIMIT OF ELEVATION
LENGTH
(m)
15
15
25
4
LARGE TUBE
OUTER DIAMETER
9,52 mm
12,7 mm
Control line length
(D) m
15
15
25
1
REQUIRED AMOUNT OF
DIFFERENCE
H
(m)
7
7
15
MIN. THICKNESS
0,8 mm
0,8 mm
Delayed fuse
10 A
10 A
20 A
10 A
-
ADDITIOONAL
REFRIGERANT
(g / m)*
10
12
20
(go on page 5)

Werbung

loading