3. Combination of outdoor units

The unit described in this manual cannot be used in combination. It is designed to be used as a single unit.
Outdoor unit model
PURY-RP200YJM-A(-BS)
PURY-RP250YJM-A(-BS)
PURY-RP300YJM-A(-BS)
4. Specifi cations
Model
PURY-RP200YJM-A PURY-RP250YJM-A PURY-RP300YJM-A
Noise level (50/60Hz)
56dB <A>
External static pressure
Total capacity
Indoor units
Model
Quantity
Standard type
Cooling mode: – 5°CDB ~ 43°CDB
Operation
Heating mode: – 20°CWB ~ 15.5°CWB
temperature
Fresh air intake type Cooling mode: 21°CDB ~ 43°CDB
Heating mode: – 12.5°CWB ~ 20°CWB
*1: The total indoor capacity of units run simultaneously is 150% or less.
*2: To enable high static pressure with RP200, RP250, RP300, set the DipSW on the main panel as follows.
SW3-9: ON, SW3-10 60Pa compatible: OFF, 30Pa compatible: ON
5. Confi rmation of parts attached
This unit includes the following parts. Please check.
For usage methods, refer to item 10.2.
1 Connecting pipe
ID ø25.4, ID ø28.58
<Low-pressure side>
Model
RP200
RP250
RP300

6. Space required around unit

1 In case of single installation
Secure enough space around the unit as shown in the fi gure on page 2.
[Fig. 6.0.1] (P.2)
<A> Top view
<B> Side view
<C> When there is little space up to an obstruction
A
Front
B
Back
C
D
(1) If the distance is 300 mm or more between the rear side and the wall
(2) If the distance is 100 mm or more between the rear side and the wall
(3) If the wall height (H) of the front, rear or side exceeds the wall height
restriction
When the height of the walls on the front, back or on the sides <H> exceeds
the wall height limit as defi ned here, add the height that exceeds the height
limit <h> to the fi gures that are marked with an asterisk.

7. Lifting method

[Fig. 7.0.1] (P.2)
Use suspension ropes that will withstand the weight of the unit.
When moving the unit, use a 4-point suspension, and avoid giving impacts
to the unit (Do not use 2-point suspension).
Place protective pads on the unit where it comes in contact with the ropes to
protect the unit from being scratched.
Set the angle of roping at 40° or less.
Use 2 ropes that are each longer than 8 meters.
Component unit model
-
-
-
57dB <A>
0 Pa *2
50~150% *1
15~250
1~20
1~25
1 pc.
1 pc.
1 pc.
Unit height
Air outlet guide (Procured at the site)
-
-
-
59dB <A>
1~30
<Wall height limit> Front: Up to the unit height
(4) If there are obstacles at the upper part of the unit
2 In case of collective installation
[Fig. 6.0.2] (P.2)
A Front
C Wall height (H)
When multiple units are installed adjacent to each other, secure enough
space to allow for air circulation and walkway between groups of units as
shown in the fi gures on page 2.
At least two sides must be left open.
As with the single installation, add the height that exceeds the height limit
<h> to the fi gures that are marked with an asterisk.
If there is a wall at both the front and the rear of the unit, install up to 6 units
consecutively in the side direction and provide a space of 1000 mm or more
as inlet space/passage space for each 6 units.
Place protective padding at the corners of the product to protect the product
from scratches or dents that might be caused by the rope.
Caution:
Be very careful when carrying/moving the product.
- When installing the outdoor unit, suspend the unit at the specifi ed location of
the unit base. Stabilize as necessary so that it does not move to the side and
support it at 4 points. If the unit is installed or suspended with 3-point support,
the unit may become unstable and fall.
Back: Up to 500 mm from the unit bottom
Side: Up to the unit height
B Must be open