12
 

11.4 Relay Module MR8

MR8 is a supplementary module which is located outside the DCC 8 plus Panel box.
The MR8 contains 8 changeover contact relays. When using all 16 zones, the DCC 8plus needs
two relay modules.
11.4.1

Configuration of the MR8:

Should zones numbered 1 to 8 be used, a jumper is set at outputs 1 - 8 of the MR8 mother board;
should the jumper be set at outputs 9 - 16, zones numbered 9 to 16 will be used.
The MR8 relay contact type (normally closed or normally open) is determined by configuring the
NO/NC outputs inside the housing. Setting the jumper at the NO output will normally open the
contact; setting the jumper at the NC output will normally close the contact.
Special Jumper 1
When this jumper is set, the first zone relay is activated by the module relays after the button
[ Silence Alarms ] on the control panel is pressed upon an alarm event.
11.4.2

Performance of the MR8:

The MR8 Relays (outside of the panel) are activated upon an alarm event (fire) in the respective
zone they are connected to.
If a "Sounder Delay" is set in the main control panel, this delay will also reflect to the relay
activation of the first alarm.
The relay activation delay is eliminated by pressing the button [ Sound Alarms ],
the relay and the sounders are immediately enabled.
If only one zone is set with a delay, than only this relay will take affect to the delay. All
other will be activated corresponding to the zones.
The relay will restore its normal state only after pressing [ Reset ] at the control panel.
Version 1.0
Attention!
Do not connect or disconnect an expander when the power is on!
Before connecting or disconnecting the expander you SHOULD check
 
whether the main and the stand-by power supplies are OFF!
Note!
The MR8 can only be connected and operated from a DCC 8 plus in "Master" mode!