7 Testing of the panel

 
Attention!
It has been assumed that prior to making the connection at the panel, the
integrity of the system ALL wiring has been comprehensively tested,
 
including insulation to earth.
 
Connect the battery leads from the power supply box to the positive and
negative battery terminals.
Switch on the mains power supply.
If the buzzer and indicator LED's are operating, press the RESET button.
In Normal Operating Mode only POWER SUPPLY 230V will be illuminated.
If in the Normal Operating Mode other LED's are illuminated and the buzzer is sounding, carefully
check all fuses and connections. Refer to the page 7 for the associated yellow LED's apply to. The
connection diagram on the inside of the external cover will assist in identifying the LED.
 
Note!
The battery might show a 'Low Battery Fault' initially until it has had time to
charge up to the required level.
Note!
If General Fault and zone 1 FAULT LED's illuminate, there is a wiring/
connection problem. Check the polarity of the connection, the connection of
 
the devices and whether a head is removed.
 
 
Test every detector per zone to assure that the alarm is indicated and
registered at the DCC 8 plus.
The connected sounder zones must activate
Note!
If General Fault and SOUNDER FAULT / DISABLE LED's illuminate, there is a
wiring / connection problem. Check the polarity of the connection of each of
the devices, the polarity of the connection of the devices to the Panel terminal
block or whether an earth fault exists.
 
Version 1.0
 
Bedienungsanleitung DCC 8 plus
9
 
 