User manual DCC 8 plus 
 

4 Indication and operator panel

 
4.1

Operator panel DCC 8 plus

 
4.2

Status condition and output

Status
Normal
Fire
General-Fault
Test/Scroll
Enable/Disable
 
Version 1.0
Indication
The green LED next to the 'Mains Power Supply' will be illuminated.
Two integrated red status FIRE LED's and a zone identification LED will
flash together on receipt of a FIRE condition and become steady after
the [ Silence Alarm ] button is pressed.
An internal buzzer will operate until silenced [ Silence Buzzer ].
The external sounders will operate until [ Silence Alarms ].
Pressing [ Silence Alarms ] a second time will reactivate the sounders.
The FIRE relay will energize.
A yellow General Fault LED will always illuminate together with an
external or internal identification LED.
An internal buzzer will sound.
The FAULT relay will de-energize.
A detailed fault description is found in chapter 4.3
The yellow LED „Test" and Zone 1 – 16 will flash twice a second after
pressing [ LED Test/Scroll ].
The internal buzzer will sound and can be deactivated by pressing
[ Silence Buzzer ]
The yellow LED „Enable/Disable" and the LEDs of the disabled zones
are illuminated at an disablement.
The yellow LED „Sounder Fault/Disable" glows if a sounder zone is
disabled.