9 Additional facilities:

 
 
8.2

To 'One Man' Test a Zone::

Press [ TEST / SCROLL ]:
Zone 1 is in Test Mode.
Press [ TEST / SCROLL ]:
2.Zone 2 is in Test Mode.
 
Continue the "One Man" Test for zones 3 - 16 by pressing [ TEST / SCROLL ]. You will leave
automatically the Test Mode when reaching the last zone, or at any time, by pressing [ RESET ].
 
8.3

To disable Sounders:

Press [ ENABLE / DISABLE ]:
Press [ TEST / SCROLL ] until:
Press [ ENABLE / DISABLE ]:
Press [ RESET ]:
8.4

To enable Sounders:

Press [ ENABLE / DISABLE ]:
Press [ TEST / SCROLL ] until:
Press [ Enable / Disable ]
Press [ RESET ]:
9.1

Class Change:

To use the class change function connect the terminals of a switch with normally open contacts to
the CC (Class Change) clamps of the main module terminal.
The working mode of the sounders will be:
when the switch is pressed - one second sounder on, one second sounder off;
when the switch is depressed - the sounder is off.
Version 1.0
 
Bedienungsanleitung DCC 8 plus
TEST AND ZONE yellow LED's will flash.
Flashing LED will move down to zone
DISABLE / ENABLE LED will flash.
Zone 1 LED will flash.
SOUNDER FAULT / DISABLE LED will flash.
DISABLE / ENABLE LED will flash.
SOUNDER FAULT / DISABLE LED
changes to steady.
ENABLE / DISABLE LED flashes.
At this point zone the sounders are
disabled.
DISABLE / ENABLE LED will flash
Zone 1 LED will flash.
No Zone LED flashes anymore,
SOUNDER FAULT / DISABLE LED is steady.
ENABLE / DISABLE LED will flash.
SOUNDER FAULT / DISABLE LED change to
flashing.
At this point zone the panel has reset.