To unmount indoor unit
(1) Remove the screw cover on the bottom surface.
(Fig. 3-104)
(2) Fasten the frame to the rear panel using the 2 supplied
tapping screws 4 x 10 mm. (Fig. 3-104)
(3) Press the 2
marks on the lower part of the indoor unit
and unlatch the tabs. Then lift the indoor unit and unmount.
(Fig. 3-103)
N OTE
Under normal conditions, the installation design calls for a less
than 2 mm gap between the air conditioner unit and the wall.
Confirm that the gap is appropriate (less than 2 mm).
3-27. Drain Hose
a)
The drain hose should be slanted downward to the
outdoors. (Fig. 3-105)
b)
Never form a trap in the course of the hose.
c)
If the drain hose will run in the room, insulate the hose with
insulation* so that chilled condensation will not damage
furniture or floors. (Fig. 3-106)
*Foamed polyethylene or its equivalent is recommended.
Do not supply power to the
WARNING
unit or operate it until all
tubing and wiring to the
outside unit are completed.
Risk of Electric Shock
SUPPLEMENT
Push
Fig. 3-103
Screw
cover
Screw
Fig. 3-104
Slant
Indoor
Drain
unit
hose
Fig. 3-105
Condensation
Insulation material
(Locally purchased)
must be used.
Fig. 3-106
25

■ Floor Standing Type (P1 Type)

Concealed Floor Standing Type (R1 Type)

3-28. Required Minimum Space for Installation and
Service
Install the unit where cooled or heated air from the unit can
circulate well in the room. Do not put obstacles which may
obstruct the air flow in front of the air intake and outlet grilles.
Horizontal view
Vertical view
min.
min.
10 cm
10 cm
min. 100 cm
min. 100 cm
Fig. 3-107
NOTE
Ensure there is adequate space for maintenance of the
electrical component box, air filter, and refrigerant tubes.
C
B
A
Air outlet
36
Air inlet
54
54
3-29. Dimensions and Part Names
Floor Standing Type (P1 Type)
1
4-ø12 holes (for fastening the indoor unit to the floor with
screws)
2
Air filter
3
Refrigerant connection outlet (liquid tube)
4
Refrigerant connection outlet (gas tube)
5
Level adjusting bolt
6
Drain outlet (20 A)
7
Power cord outlet (downward, rear)
8
Refrigerant tubing outlet (downward, rear)
9
Location for mounting the remote controller (remote
controller can be attached within the room)
Table 3-3
Unit: mm
Length
Liquid
Gas
A
B
C
tube
tube
Type
22, 28, 36
1065
665
632
ø6.35
ø12.7
45, 56
1380
980
947
73
ø9.52
ø15.88
26 15
161
57
100 177
230
Side panel
Refrigerant tubing space for
downward tubing
156
67
76
213
615
260
155
107
205
Unit: mm
Rear-tube outlet
Fig. 3-108
26