3. HOW TO INSTALL THE INDOOR UNIT

■ Low Silhouette Ducted Type (Type F1)

3-1. Required Minimum Space for Installation and Service

● This air conditioner is usually installed above the ceiling so that the indoor unit and ducts are not visible. Only the air intake and air
outlet ports are visible from the unit bottom.
Minimum space for installation and service
Type
36, 45, 50
A (Length)
867
● It is recommended that space be provided (450 × 450 mm) for checking and servicing the electrical system.
Detailed dimensions of indoor unit
Type
A
36, 45, 50
867
60, 71
1,067
100, 125, 140
1,467
g
172
e
h
Unit: mm
60, 71
100, 125, 140
1,067
1,467
B
C
800
450 (Pitch 150 × 3)
1,000
750 (Pitch 150 × 5)
1,400
1,050 (Pitch 150 × 7)
Air intake port side
j
A (Suspension bolt pitch)
B
33.4
D
C
E (Flange O.D.)
54
Air outlet duct side
A (Suspension bolt pitch)
Min.
Indoor unit
250
Unit: mm
D
E
F
71
592
12
21
792
16
71
1,192
20
a) Refrigerant tubing joint (liquid tube)
b) Refrigerant tubing joint (gas tube)
c) Upper drain port VP25 (O.D. 32 mm)
200 mm flexible hose supplied
d) Bottom drain port VP25 (O.D. 32 mm)
e) Suspension lug (4 – 12 × 30 mm)
f ) Power supply outlet
g) Fresh air intake port (ø150 mm)
h) Flange for flexible air outlet duct
i ) Electrical component box
j ) Filter
Inspection
access
450 × 450
(Field supply)
(150)
D
a
154
33.4
9
Electrical
component box
Inspection
access
450 × 450
Refrigerant
tubing
Min.650
Unit: mm
290
f
255
i
c
d
26.1
70
90
b
23
140
23
Unit: mm