5.1.5
5.1.6
E
5.1.7
N
G
L
I
S
5.1.8
H
5.1.9
5.1.10
26
5 - PROGRAMMING
Feed water hardness (H)
Not visualised in time clock mode: [7 - - 1). Default setting: [H - 15]
This setting is identified by the letter H. It enables the regulation of the feed water hardness.
The system uses this setting and the previous one to establish softened water capacity.
i.e.: 25°tH
Regeneration time
Not visualised in immediate metered mode: [7--2]
It allows setting of the regeneration time. The two dots between hour and minute display do not
flash in order to differentiate with the current time display.
i.e.: regeneration at 2 :00 A.M.
Indexing the day of the week at the installation
Visualised only in mode: [7- - 5]
This parameter is identified by the display "dAy", it allows the valve to define the day of the
week, so it must be properly indexed at the installation of the softener on site.
dAy 1= monday
dAy 4= thursday
dAy 2= tuesday
dAy 5= friday
dAy 3= wednesday
dAy 6= saturday
Day override
This setting is identified by the letter A. It allows to set the maximum amount of days that the
system can stay in service mode without a regeneration. This stage is compulsory for a valve in
time clock mode and optional for a valve in metered mode.
i.e.: - regeneration every 7 days
- cancelled stage
Regeneration cycles
The settings 8-1 to 8-6 enable the regulation of the regeneration cycle times.
The amount of cycles is established by the piston type. (View stage 2).
i.e.: Cycle 1- 8mn
Cycle 2- 65mn
Cycle 3- 4mn
DF
1) Backwash
2) Brine draw/Slow rinse
3) 2
nd
backwash
4) Fast rinse
5) Brine refill

Define days of regeneration in the week

Visualised only in mode: [7- - 5]
This parameter is identified by the letter "d". It allows you to select the days of the week that
trigger regeneration. If every day is set to 0, the valve does not regenerate and displays an error
code Err2 after eighth day. To clear this error display: settle at least one day of the week and / or
trigger a manual regeneration.
dAy 7 = sunday
dFFF
1) Brine refill
2) Pause (salt saturation)
3) Backwash
4) Brine draw/Slow rinse
5) 2
backwash
nd
6) Fast rinse
[H - 25]
[ 2 : 0 0 ]
[ A - - 7 ]
[AOFF]
[1 - - 8]
[2 - 65]
[3 - - 4]
FLtr
1) Backwash
2) Fast rinse