CONDENSATE DRAIN PAN
The MAJOR LINE is equipped with a sloping polymer pan which does not retain
water, fitted with a Ø22 mm external drain end piece and a plug.
When the unit is delivered, the pan is blocked on both sides (2 plugs), so it is
therefore imperative that the plug is removed from the side where the hydraulic
connection is to be made.
If the hydraulic connection side is switched, do not forget to refit the
!
plug to the other side.
The connection can be made on the left or right-hand side of the unit. The drain hose
can be separate for each unit or corrected to a main drain hose. Use a clear and/or
rigid drain pipe for a minimum slope of 1 cm/m, with a
constant gradient along its whole length. Install a trap measuring at least 5 cm to
prevent unpleasant gases or odours exiting the hose.
An auxiliary pan must be installed on the connection side using the 2 screws (fig.
11, a).
CONDENSATE DRAIN PUMP
The MAJOR LINE can be equipped with a condensate drain pump.
Its technical specifications are as follows:
Maximum flow rate of 16 l/h for a head height of 2 metres and a maximum pipe
l
length of 5 metres.
Maximum flow rate of 15 l/h for a head height of 2 metres and a maximum pipe
l
length of 10 metres.
The operation points are provided in the table below.
Table of actual flow rates for the SI 10 pump with Ø 6 mm PVC internal pipe.
Discharge height
0 m
2 m
4 m
6 m
8 m
10 m
Warning: Make sure that the flow of water to be discharged in the thermal selection
is suitable for your application
Pipe length (ø int. 6 mm)
5 m
10 m
20
19
16
15
11.5
11
8.5
6
4
EN - 8
20 m
30 m
18
17
14
13.5
10.5
10
7.5
6.5
5
4
3.5
2.5