"SMMS wave tool" is an application software ("Application") for the Android OS smartphone and for those who
install and do maintenance to the compatible air conditioning equipment. The Application enables checks of some
of the system and data and test operations of compatible air conditioning equipment. Please check the information
about compatible air conditioning equipment and smartphone from the below URL. Be sure to read
the Operating Manual before the use of this Application, "SMMS wave tool". You can download the
Application and the Operating Manual from the below URL or QR code. QR code is a trademark
or registered trademark of DENSO WAVE Inc.Android is a trademark or registered trademark of
Google Inc.
URL : http://www.toshiba-carrier.co.jp/global/appli/smms_wave_tool/
NOTICE
• This Application enables the auto-address setup and the test operation of the outdoor unit by smartphone in
48 hours from the power input to the outdoor unit.
• You should decide whether to make use of this auto-address setup and test operation function at its own
responsibility and also be sure to confirm notices in the Operating Manual before performing the test operation.
• If you want to disable the function of the auto-address setup and the test operation, perform the following
operations.
• Refer to the service manual for setting change of the auto-address setup and the test operation function to be
effective.
Switch setting of some functions prohibition
Rotary switch
Step
SW01
SW02
SW03
(1)
2
1
14
(2)
2
1
14
Press for more than 5 secs
(3)
1
1
1
* Do it again if the 7-segment display is different from the above.
* The functions other than the auto-address setup and test operation of this Application can work normally even if
the auto-address set up and test operation function are disabled.
CAUTION
• High voltage parts exist in the electrical control box.
If you set Switch setting, set it from the access door cover of the electrical control box cover to avoid electric
shock.
• After finishing operations, slide the access door cover to the position before and fix it with the screw.
Access
Cover of the electrical
door cover
control box
Fixing screw for the
access door cover
HOW TO USE
• This Application uses the NFC (Near Field
Communication) function of smartphone.
• For the use, hold your smartphone to the
"TOUCH" mark of the outdoor unit.
• Refer to the Operating Manual of the "SMMS
wave tool" for the details.
179-EN
1117701001-EN.indd 90
1117701001-EN.indd 90
Push switch
7-segment display
Condition
SW04
[ A ] [ B ]
-
[ nf ] [ c.00 ]
Setting preparation
[ nf ] [ c.01 ]
Setting completion
-
[ U.1. ] [ - - - ]
Return the switch
SW04
SW05
SW15
Push switch
D600 D601 D602 D603
D604
7-segment
7-segment
display [A]
display [B]
SW01
SW02
SW03
Rotary switches
Outdoor unit
NFC receiver for
SMMS wave tool
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be installed
requires a design that in the event of refrigerant gas
leaking out, its concentration will not exceed a set
limit.
The refrigerant R410A which is used in the air conditioner
is safe, without the toxicity or combustibility of ammonia,
QR code
and is not restricted by laws to be imposed which protect
the ozone layer. However, since it contains more than air, it
poses the risk of suffocation if its concentration should rise
excessively.
Suffocation from leakage of R410A is almost non-existent.
With the recent increase in the number of high concentration
buildings, however, the installation of multi air conditioner
systems is on the increase because of the need for effective
use of floor space, individual control, energy conservation
by curtailing heat and carrying power etc.
Most importantly, the multi air conditioner system is able to
replenish a large amount of refrigerant compared with
conventional individual air conditioners. If a single unit of the
multi conditioner system is to be installed in a small room,
select a suitable model and installation procedure so that if
the refrigerant accidentally leaks out, its concentration does
not reach the limit (and in the event of an emergency,
measures can be made before injury can occur).
In a room where the concentration may exceed the limit,
create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak detection
device.
The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m
≤ Concentration limit (kg/m
The concentration limit of R410A which is used in multi air
conditioners is 0.3kg/m
.
3
NOTE 1 :
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should be
as charged in each independent device.
e.g., charged
amount (10kg)
Room A Room B Room C Room D Room E Room F
For the amount of charge in this example:
Smartphone
The possible amount of leaked refrigerant gas in rooms
A, B and C is 10kg.
The possible amount of leaked refrigerant gas in rooms
D, E and F is 15kg.
– 90 –
Important
NOTE 2 :
The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas
(opening without a door, or an opening 0.15% or
larger than the respective floor spaces at the top or
bottom of the door).
(3) If an indoor unit is installed in each partitioned
room and the refrigerant piping is interconnected,
the smallest room of course becomes the object.
But when a mechanical ventilation is installed
interlocked with a gas leakage detector in the
smallest room where the density limit is exceeded,
the volume of the next smallest room becomes the
object.
)
3
3
)
Very
small
room
Small
Medium
room
room
Mechanical ventilation device - Gas leak detector
NOTE 3 :
Outdoor unit
The minimum indoor floor area compared with the
e.g.,
amount of refrigerant is roughly as follows:
charged amount (15kg)
(When the ceiling is 2.7m high).
40
Range below the
35
m
2
density limit of
0.3 kg/m
3
30
(countermeasures
not needed)
25
Indoor unit
20
15
10
5
0
10
20
Total amount of refrigerant
Outdoor unit
Refrigerant piping
Indoor unit
Refrigerant piping
Outdoor unit
Indoor unit
Large room
Range above the
density limit of
0.3 kg/m
3
(countermeasures
needed)
30
kg
180-EN