  • DEUTSCH, seite 15
¿ Caution to connection of indoor
unit
When connecting the indoor units to a single port type
FS unit and a branch of multi port type FS unit, it is
necessary to set up the CODE No..
• When connecting the indoor units to a single
port type FS unit and a branch of multi port type
FS unit, group control and individual control are
available.
[ 0E ] : Group setting
0 : Individual (Factory default)
1 : Group
[ FE ] : Branching system address (1~64)
• Should not be duplicate in one system
• Factory default : 99
[ FD ] : Priority operation mode
0 : Heating prioritized (Factory default)
1 : Cooling prioritized (The cooling is
prioritized even if setting only one unit in
one branching)
¿ [ Set up example ]
< In case of connecting one indoor unit>
Single port type FS unit
Piping
Indoor unit
Control wiring
between indoor
Remote
unit and FS unit
controller
(Within 15 m)
[ 0E ] : It is not necessary to set up
[ FE ] : It is not necessary to set up
[ FD ] : It is not necessary to set up
Multi port type FS unit
Piping
Indoor unit
Remote
controller
[ 0E ] : It is not necessary to set up
[ FE ] : It is not necessary to set up
[ FD ] : It is not necessary to set up
167-EN
1117701001-EN.indd 84
1117701001-EN.indd 84
<In case of connecting one group operation of
indoor units>
Single port type FS unit
Piping
Indoor unit
Control wiring
between indoor
Remote controller
unit and FS unit
(Within 15 m)
Group control
[ 0E ] :
1
1
1
[ FE ] :
It is not necessary to set up
[ FD ] :
It is not necessary to set up
Multi port type FS unit
Piping
Indoor unit
Remote controller
Group control
[ 0E ] :
1
1
1
[ FE ] :
It is not necessary to set up
[ FD ] :
It is not necessary to set up
<In case of connecting two group operations of
indoor units>
Single port type FS unit
Piping
Indoor unit
Control wiring
Remote
between indoor
controller
unit and FS unit
(Within 15 m)
Group control
Group control
[ 0E ] :
1
1
1
1
[ FE ] :
1
1
1
1
[ FD ] :
0
0
0
0
Multi port type FS unit
Piping
Indoor unit
Remote
controller
Group control
Group control
[ 0E ] :
1
1
1
1
[ FE ] :
1
1
1
1
[ FD ] :
0
0
0
0
<In case of connecting one group operation of
indoor units and two indoor units>
Single port type FS unit
Piping
Indoor unit
Control wiring between
Remote
indoor unit and FS unit
controller
(Within 15 m)
Group control
[ 0E ] :
1
1
0
[ FE ] :
1
1
1
[ FD ] :
0
0
0
Multi port type FS unit
Piping
Indoor unit
Remote
controller
Group control
[ 0E ] :
1
1
0
[ FE ] :
1
1
1
[ FD ] :
0
0
0
<In case of connecting four indoor units>
Single port type FS unit
Piping
Indoor unit
Control wiring between
indoor unit and FS unit
(Within 15 m)
Remote controller
[ 0E ] :
0
0
0
[ FE ] :
1
1
1
[ FD ] :
0
0
0
Multi port type FS unit
Piping
Indoor unit
Remote controller
[ 0E ] :
0
0
0
[ FE ] :
1
1
1
[ FD ] :
0
0
0
– 84 –
<Incorrect connection examples>
Incorrect
Single port type FS unit
Single port type
FS unit
Piping
Indoor unit
Control wiring
Remote controller
between indoor
unit and FS unit
0
(Within 15 m)
1
Group control
0
Incorrect
Multi port type FS unit
Single port type FS unit
Piping
Remote controller
Group control
0
Incorrect
1
0
Multi port type FS unit
Multi port type FS unit
Piping
Indoor
unit
Remote controller
Group control
0
1
Incorrect
0
Multi port type FS unit
Piping
Indoor
unit
Remote controller
Group control
0
1
0
Indoor
unit
168-EN
2/26/2559 BE 11:48 AM
2/26/2559 BE 11:48 AM

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis