Full opening of the valve
Open the valves of the outdoor unit fully.
MAP080
MAP100
Packed valve
Balance pipe
Using a 4 mm-hexagonal wrench, fully open the valve shaft.
Ø12.7 packed valve
Using a 4 mm-hexagonal wrench, fully open the
valve shaft.
Liquid side
Ball valve
Using a flathead screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)
Service port
Discharge gas
side
(1)
(2)
Ball valve
Using a wrench, turn the valve shaft counterclockwise by 90° until it hits the stopper. (Full open)
Suction gas side
141-EN
1117701001-EN.indd 71
1117701001-EN.indd 71
MAP120
MAP140
MAP160
MAP180
MAP200
Ø15.9 packed valve
Using a 5 mm-hexagonal wrench, fully open the
valve shaft.
Position of screwdriver slot
Fully closed
Fully opened
Valve unit
Using flathead screwdriver, turn
it counterclockwise by 90° until
it hits the stopper. (Full open)
Slot
* When opened fully, do not apply excessive
Flare nut
torque after the screwdriver hits the
stopper; otherwise a problem may be
caused on the valve. (5 N•m or less)
Fully closed
Fully opened
– 71 –
F-GAS label
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol
• Chemical Name of Gas
• Global Warming Potential (GWP) of Gas
CAUTION
1. Stick the enclosed refrigerant label adjacent to the charging and/or recovering location.
2. Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink. Then, place the
included transparent protective sheet over the label to prevent the writing from rubbing off.
3. Prevent emission of the contained fluorinated greenhouse gas. Ensure that the fluorinated greenhouse gas is
never vented to the atmosphere during installation, service or disposal. When any leakage of the contained
fluorinated greenhouse gas is detected, the leak shall be stopped and repaired as soon as possible.
4. Only qualified service personnel are allowed to access and service this product.
5. Any handling of the fluorinated greenhouse gas in this product, such as when moving the product or recharging
the gas, shall comply under (EC) Regulation No. 842/2006 on certain fluorinated greenhouse gases and any
relevant local legislation.
6. Periodical inspections for refrigerant leaks may be required depending on European or local legislation.
7. Contact dealers, installers, etc., for any questions.
Pre-charged Refrigerant at Factory [kg],
R410A
specified in the nameplate
kg
Additional Charge on Installation Site
[kg]
kg
kg
R410A
1975
142-EN
2/26/2559 BE 11:48 AM
2/26/2559 BE 11:48 AM