Air conditioner (multi type)/outdoor unit
Vorschau ausblenden Andere Handbücher für MMY-MAP0806FT8P-E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 15
5. Be careful of the connecting arrangement of the header unit and follower units. Set the outdoor units in order of
capacity from the one with the largest capacity. (A (Header unit) ≥ B ≥ C)
• Be sure to use a header unit for the leading outdoor unit to be connected to the main pipe. (Figure 1, 3 and 6)
• Be sure to use a T-shaped branch joint (RBM-BT14FE/RBM-BT24FE: separately purchased) to connect each
outdoor unit.
• Be careful of the direction of the Outdoor unit connection piping kit for the liquid side. (As shown in Figure 2, a
Outdoor unit connection piping kit cannot be attached so that the refrigerant of the main pipe flows directly into
the header unit.)
• When attaching a Y-shaped branch unit for the outdoor unit connection piping kit, attach it level with the
ground (Be sure not to exceed ±15 degrees.). Regarding a T-shape branch joints for the liquid side, there is no
restriction for its angle.
(Horizontal line)
Within ±15 degrees
A
(A arrow view)
B
• In case of using the Y-shaped branching joint for connecting between
outdoor units (Discharge gas joint and Suction gas joint), please keep
the straight part of at least 500mm at the inlet.
Discharge side gas piping / Liquid piping
q Figure 1
Correct
Header unit A
Follower unit B
Follower unit C
Main pipe
Liquid joint
To indoor unit
Discharge gas joint
Suction side gas piping
q Figure 3
Correct
Header unit
Follower unit
Follower unit
A
B
C
Main pipe
To the indoor unit
Suction gas joint
121-EN
1117701001-EN.indd 61
1117701001-EN.indd 61
At a level position
(Horizontal line)
Do not connect
Within ±15
a branch unit
degrees
vertically.
(B arrow view)
q Figure 2
Incorrect
Header unit A
Follower unit B
Follower unit C
Liquid joint
To indoor unit
Main pipe
Discharge gas joint
[Inverse connection of suction gas joint]
q Figure 4
Incorrect
Header unit
Follower unit
Follower unit
A
B
C
Main pipe
To the indoor unit
Suction gas joint
– 61 –
<Upright connection of suction gas joint>
q Figure 5
Incorrect
Header unit A
Follower unit B
Suction gas joint
Main pipe
A
To indoor unit
Vertical line
Suction gas joint
<When drawing pipes downward>
q Figure 6
Correct
Header unit
Follower unit
Follower unit
A
B
C
L-shaped
Main pipe
pipe
To the indoor unit
Suction gas joint
A view
Unit
[Vertical connection of branch units]
q Figure 7
Incorrect
Suction gas
Suction gas
joint
joint
122-EN