5. Quick Parameter List
Parameter No.
Description
n01
Parameter access:
0: Limited parameter access
1: Full parameter access
8: Factory parameter initialise
n02
Run command selection:
0: Digital operator
1: Control circuit terminal
2: Communication (option)
n03
Frequency reference selection:
0: Digital operator (potentiometer)
1: Frequency reference 1 (n21)
2: Control circuit terminal (0 to 10V)
3: Control circuit terminal (4 to 20mA)
4: Control circuit terminal (0 to 20mA)
6: Communication (option)
n09
Maximum output frequency
n10
Maximum output voltage
N11
Maximum voltage output frequency
n16
Acceleration time 1
n17
Deceleration time 2
n21
Frequency reference 1
n22 - n28
Frequency reference 2 - 8
n32
Motor rated current
n36 - n39
Multi-function input (S2 -S5)
n40
Multi-function output (MA-MB-MC)
n44
Multi-function analog output (AM-AC):
0: Output frequency (10V/Max, freq.)
1: Output current (10V/Inverter rated current)
n46
Carrier frequency
n52
DC injection braking current
n53
DC injection braking at stop
n54
DC injection braking at start
n55
Stall prevention during deceleration:
0: Enabled
1: Disabled
Multi-function Inputs
*1
Value
Function
2
Reverse/Stop
3
External Fault (NO)
4
External Fault (NC)
5
Faul reset
6
Multi-step speed reference 1
7
Multi-step speed reference 2
*1 Refer to user's manual for complete list
*1
Range
0 to 9
0 to 2
0 to 4, 6
50 to 400Hz
1 to 255V (200V class)
1 to 510V (400V class)
50 to 400Hz
0.0 to 999sec
0.0 to 999sec
0.0 to 400Hz
0.0 to 400Hz
Depending on model
0 to 35
0 to 18
0,1
1 to 4 (2.5 - 10kHz)
7 to 9 (Proportional to
output freq.)
0 to 100%
0 to 100%
0 to 100%
0,1
Multi-function Outputs
*1
Value
Function
0
Fault Output
1
During Run
2
Frequency agree
6
Overtorque being monitored (NO)
12
RUN mode
13
Inverter ready
Default
1
0
0
200 (200V class)
400 (400V class)
10sec
10sec
50Hz
0Hz
0 to 120% of inverter rated
output current
--
1
0
Depending on model
50%
50%
50%
0

Werbung