INSTALLATION OF INDOOR UNIT
Installation of indoor unit
• Attach the nut (M10 or W3/8: Procured locally) and washer
(34 mm (diam.)) to the hanging bolt.
• Put washers at either side of the T-groove on the hanging
bracket of the indoor unit in order to hang the unit.
• Using a spirit level, check that all four sides are horizontal.
(Horizontal positioned within 5 mm)
• Cut off the installation gauge from the installation pattern.
• Using the installation gauge check and adjust clearance
between the indoor unit and the ceiling opening (1)
(10 to 42 mm on each side).
Ensure that the unit is level to the ceiling and within a
distance of (2) 23 mm to 28 mm below.
The installation gauge has details of how to use printed on it.
Note) Install the indoor unit so that the end part of opening
does not come into contact with the drain socket piping.
Level vial (Horizontal: within 5 mm)
Indoor unit
Hanging bolt
Hanging
23 to 28
metal
10 to 42
mm (2)
Installation gauge
Ceiling board
REQUIREMENT
Before installation of the indoor unit be sure to
remove the transportation cushion found between
the fan and the bell mouth.
Running the unit without removing the cushion
may damage the fan motor.
Be sure to remove the cushion for transportation
between the fan and the bell mouth.
mm (1)
Indoor unit
Ceiling board
Installation gauge
Install the ceiling panel after completion of the
installation of the indoor unit, including all piping and
wiring.
Install the ceiling panel as per the supplied Installation
Manual.
Check the installation dimensions of the indoor unit
and the ceiling opening are correct and then install.
9
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Nut
(W3/8 or M10)
(1) M10 washer supplied, all other material
must be procured locally.
(2) To ensure that the unit is mounted safely, the
hanging bolt must be positioned just below
the hanging bracket as shown in the diagram.
1) 23 to 28
mm
2) 10 to
42 mm
Installation of ceiling panel
(Sold separately)
REQUIREMENT
Ensure the ceiling panel is mated to the ceiling
surface or the indoor unit.
If the panel and unit are not mated together this
may result in the formation of dew condensation
causing a possible water leak.
First remove the 4 corner caps from the ceiling
panel and fit to the indoor unit.
(1)
M10 flat washer
(Accessory)
(2)
M10 flat washer
(Accessory)