5.4
TTF300-E5XX, non-sparking ATEX + dust
explosion protection
Explosion protection
The TTF300 complies with the requirements of
ATEX directive 94/9/EC
Approved for use in Zone 2/22
Designation
II 3G EEx nA II T6
II 3 D IP 65 T 135 °C
ABB manufacturer's declaration in accordance with ATEX directive
Temperature table
Temperature
Device category 3 use
class
T6
-50 ... 56 °C (-58 ... 132.8 °F)
T5
-50 ... 71 °C (-58 ... 159.8 °F)
T4
-50 ... 85 °C (-58 ... 185.0 °F)
5.5

TTF300-D1XX, dust explosion protection

Explosion protection
Approved for use in dust/Zone 20.
Designation
II 1 D IP 65 T 135°C
EC prototype test certificate BVS 06 ATEX E 029
5.6
TTF300-D2XX, dust explosion protection +
intrinsic safety
Explosion protection
Approved for use in dust/Zone 20 and gas/Zone 0.
Designation
II 1 D IP 65 135°C
II 1G EEx ia IIC T6
EC prototype test certificate BVS 06 ATEX E 029
EC prototype test certificate PTB 05 ATEX 2017 X
5.7

TTF300-E3XX, flameproof enclosure

Explosion protection
Approved for use in Zone 1.
Designation
II 2G EEx d IIC T6
EC prototype test certificate PTB 99 ATEX 1144
5.8
TTF300-E4XX, flameproof enclosure +
intrinsic safety
Explosion protection
Approved for use in Zone 1.
Designation
II 2G EEx d IIC T6
II 1G EEx ia IIC T6
EC prototype test certificate PTB 99 ATEX 1144
EC prototype test certificate PTB 05 ATEX 2017 X
5.9

TTF300-L1XX, intrinsically safe FM

Class I, Div. 1 + 2, Groups A, B, C, D T6
Class II, Groups E, F, G; Class III
Class I, Zone 0, AEx ia IIC T6
Product variant: TTF300-L1
Control drawing: 214832
CI/TTF300-X1

5.10 TTF300-L2XX, non-incendive FM

Class I, Div. 2, Groups A, B, C, D
Class II, Groups E, F, G; Class III
Control drawing: 214830

5.11 TTF300-L3XX, explosion proof FM

XP,NI, DIP Class I, II, III, Div. 1 + 2, Groups A-G, factory sealed
Control drawing: 214866
5.12 TTF300-L7XX, explosion proof +
Intrinsically Safe FM
XP,NI, DIP Class I, II, III, Div. 1 + 2, Groups A-G, factory sealed
Control-Drawing: 214866
Class I, Div. 1 + 2, Groups A, B, C, D T6
Class II, Groups E, F, G; Class III
Class I, Zone 0, AEx ia IIC T6
Control drawing: 214832

5.13 TTF300-R1XX, intrinsically safe CSA

Class I, Div. 1 + 2, Groups A, B, C, D
Class II, Groups E, F, G; Class III
Control drawing: 214825

5.14 TTF300-R2XX, non-incendive CSA

Class I, Div. 2, Groups A,B,C,D
Class II, Groups E, F, G; Class III
Control-Drawing: 214827

5.15 TTF300-R3XX, explosion proof CSA

XP,NI, DIP Class I, II, III, Div. 1 + 2, Groups A-G, factory sealed
Control drawing: 214866
5.16 TTF300-R7XX, explosion proof +
Intrinsically Safe CSA
XP,NI, DIP Class I, II, III, Div. 1 + 2, Groups A-G, factory sealed
Control-Drawing: 214866
Class I, Div. 1 + 2, Groups A, B, C, D
Class II, Groups E, F, G; Class III
Control-Drawing: 214825
TTF300
Ex relevant specifications
EN - 31