Slim Duct Type
Opening hole on ceiling
and placing of hanging bolt
• Considering the indoor unit and the hanged-up
piping/wiring work, determine the installation
position and direction.
• After installation position of the indoor unit has
been determined, open a hole on the wiring and
place the hanging bolt.
• For opening size of the ceiling and the hanging
bolt pitch, see the external view.
• When the ceiling has already boarded, draw the
drain pipe, refrigerant pipe, inter-unit wire
between indoor and outdoor units, central
control system wire, and remote controller wire
up to the position where pipes and wires are
connected before hanged-up the indoor unit.
The hanging bolts and nuts will be procured
locally.
Hanging bolt
Nut
Installation of hanging bolt
Use M10 hanging bolts (4 pcs, to be local
procure).
Matching to the existing structure, set pitch
according to size in the unit external view as
shown below.
Install the bolts with insert brackets or anchor bolts.
(Blade type
bracket)
Use existing angles or install new support angles.
Use a hole-in anchors, hole-in plugs, or a hole-in bolts.
9-EN
M10 or W3/8
4 pieces
M10 or W3/8
12 pieces
New concrete slab
Anchor bolt
(Slide type
(Pipe hanging
bracket)
anchor bolt)
Steel flame structure
Hanging bolt
Hanging bolt
Support angle
Existing concrete slab

Installation of indoor unit

• Attach the nuts (M10 or W3/8: Procured locally)
and the attached washers (Ø34) to the hanging
bolt.
• Put washers at up and down of T-groove of the
hanging bracket of the indoor unit to hang down
the indoor unit.
• Using a level vial, check that four sides are
horizontal. (Horizontal degree: Within 5mm)
Hanging bolt
(W3/8 or M10)
(1) Required those other than M10 flat washer at site.
(2) To prevent falling-off of bolt (safety), be sure to set it just
under the hanging bracket as shown in the figure.
(910mm × 511mm)
Rubber
– 9 –
Installation Manual
(1)
M10 flat washer
(Accessory)
Nut
(2)
(W3/8 or M10)
M10 flat washer
Nut
(Accessory)
(W3/8 or M10)