Connecting an external contact, for example, a room
thermostat or a timer allows you to temporarily or peri-
odically raise or lower the room temperature. When the
contact is on, the heat curve offset is changed by the
number of steps selected in the menu. If a room sensor
is installed and activated the desired room temperature
(°C) is set.
MENU 1.30.4 - LOWEST SUPPLY HEATING
heating
Setting range: 5 - 80 °C
Set the minimum temperature on the supply temperat-
ure to the climate system. This means that
ECS 40/ECS 41 never calculates a temperature lower
than that set here.
MENU 1.30.5 - LOWEST SUPPLY COOLING
cooling
Depending on which cooling accessory is used, the
setting range can vary.
Alarm, room sensor during cooling operation
Set the minimum temperature on the supply temperat-
ure to the climate system. This means that
ECS 40/ECS 41 never calculates a temperature lower
than that set here.
Here, you can receive alarms during cooling operation,
for example if a room sensor malfunctions.
NOTE
Cooling flow line must be set with regard to
which climate system is connected. For ex-
ample, floor cooling with too low cooling flow
line can cause condensation precipitation,
which in the worst instance could lead to
moisture damage.
MENU 1.30.6 - HIGHEST SUPPLY HEATING
climate system
Setting range: 5 - 80°C
Set the highest supply temperature for the climate sys-
tem here.
Caution
With underfloor heating systems, "Maximum
supply temperature for heating" should nor-
mally be set between 35 and 45°C.
Check the max floor temperature with your
floor supplier.
32
MENU 1.30.7 - OWN CURVE
Own curve, heating
Caution
Curve 0 must be selected for own curve to
apply.
You can create your own heating curve here, if there
are special requirements, by setting the desired supply
temperatures for different outdoor temperatures.
Supply temp
Setting range: 5 – 80 °C
Own curve, cooling
Caution
Curve 0 must be selected for own curve to
apply.
You can create your own cooling curve here, if there are
special requirements, by setting the desired supply
temperatures for different outdoor temperatures.
Supply temp
Setting range: -5 – 40 °C
MENU 7.2.4 - EXTRA CLIMATE SYSTEM (ECS)
use in cooling mode
Setting range: on/off
mixing valve amplifier
Setting range: 0,1 – 10,0
mixing valve step delay
Setting range: 10 – 300 s
The shunt amplification and shunt waiting time for the
different extra climate systems that are installed are
also set here.
MENU 7.5.3 - FORCED CONTROL
Here you can force control the various components in
the installation. The most important safety functions
remain active however.
NOTE
Forced control is only intended to be used for
troubleshooting purposes. Using the function
in any other way may cause damage to the
components in your climate system.
ECS 40/ECS 41 | GB