Electrical connection

NOTE
All electrical connections must be carried out
by an authorised electrician.
Electrical installation and wiring must be carried
out in accordance with the stipulations in force.
The climate unit must not be powered when
installing ECS 40/ECS 41.
• To prevent interference, sensor cables to external
connections must not be laid close to high voltage
cables.
• The minimum area of communication and sensor
cables to external connections must be 0,5 mm² up
to 50 m, for example EKKX, LiYY or equivalent.
• ECS 40/ECS 41 must be installed via an isolator
switch. The cable area has to be dimensioned based
on the fuse rating used.
• Mark the relevant electrical cabinet with a warning
about external voltage, in those cases where a com-
ponent in the cabinet has a separate supply.
• ECS 40/ECS 41 restarts after a power failure.
The electrical circuit diagram is at the end of this Installer
handbook.
CABLE LOCK
Use a suitable tool to release/lock cables in terminal
blocks.
3
3
1
1
2
1
4
1
2
3
100
1
2
2
2
4
3
OVERVIEW ACCESSORY BOARD (AA5)
AA5-S2
AA5-X2
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
-X8
-X2
-X4
1
2
3
4
5
6
7
8
AA5-X4
AA5-X10
ELECTRICAL CONNECTION VERSIONS F1345
F1345 has different electrical connection versions de-
pending on when the heat pump was manufactured. To
check which electrical connection applies to your F1345,
check the designation "2.0" visible above the right hand
side of the terminal block as illustrated.
CONNECTING COMMUNICATION
If several accessories are to be connected, or are already
connected, the following cards must be connected in
series with the previous card.
Use cable type LiYY, EKKX or similar.
This accessory contains an accessory board (AA5) that
must be connected directly to the compatible product
on the input board (terminal block AA3-X4). For F1345
without electrical connection version 2.0 on X6 and for
F1345 with electrical connection version 2.0/F1355 on
terminal block AA101:10.
AA5-X9
-X9
9
9
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
-X10
-X1
N
L
PE
PE
AA5-X1
ECS 40/ECS 41 | GB