Program Settings; Menu System - Nibe ECS 40 Installateurhandbuch

Zusätzlicher heiz- und kühlkreis
Vorschau ausblenden Andere Handbücher für ECS 40:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Program settings

Program setting of ECS 40/ECS 41 can be performed
via the start guide or directly in the menu system.
START GUIDE
The start guide appears at first start-up after installation
of the heat pump/indoor module, but is also found in
menu .7.7.

MENU SYSTEM

MENU 7.2.1 - ADD/REMOVE ACCESSORIES
Add or remove accessories here.
Select: "Climate system 2-8".
MENU 1.1 TEMPERATURE
You make temperature settings for your installation here.
MENU 1.3 - ROOM SENSOR SETTINGS
Factor system heating
Setting range: 0,0 - 6,0
Factor system cooling
Setting range: 0,0 - 6,0
Controlling room sensor
Setting range: on/off
Name room sensor
Setting range: a-z
Activate room sensors to control the room temperature
here.
You can connect up to four room sensors to each cli-
mate system, and you can give each sensor a unique
name.
The sensor in each climate system that is furthest from
the set temperature takes control; the compatible
product tries to keep the temperature down in the room
whose sensor is furthest from the set value.
Caution
A slow heating system such as underfloor
heating may be inappropriate for controlling
with room sensors.
Factor system
You can also set a factor that determines by how much
the difference between the desired and current room
temperature will affect the supply temperature to the
climate system. A higher value gives a greater and faster
change in the cooling curve's set offset.
ECS 40/ECS 41 | GB
Caution
Too high a set value for "factor system" can
result in an uneven room temperature.
MENU 1.30.1 - CURVE, HEATING
Curve, heating
Setting range: 0 - 15,0
In menu "Curve, heating" you can view the heating curve
for your house. The task of the heating curve is to give
an even indoor temperature, regardless of the outdoor
temperature. It is from this heating curve that
ECS 40/ECS 41 determines the temperature of the water
to the climate system, the supply temperature, and
therefore the indoor temperature. Here, you can select
heating curve and read off how the supply temperature
changes at different outdoor temperatures.
TIP
It is also possible to create your own curve.
This is done in menu 1.30.7.
Caution
With underfloor heating systems, the maxim-
um supply temperature should normally be set
between 35 and 45 °C.
Check the max floor temperature with your
floor supplier.
TIP
Wait 24 hours before making a new setting,
so that the room temperature has time to sta-
bilise.
If it is cold outdoors and the room temperature
is too low, increase the curve slope by one in-
crement.
If it is cold outdoors and the room temperature
is too high, lower the curve slope by one incre-
ment.
If it is warm outdoors and the room temperat-
ure is too low, increase the curve offset by one
increment.
If it is warm outdoors and the room temperat-
ure is too high, lower the curve offset by one
increment.
MENU 1.30.3 - EXTERNAL ADJUSTMENT
Climate system
Setting range: -10 to +10
Setting range (if room sensor is installed): 5 - 30°C
31