Please read
immediately

1.1 Important information:

ATTENTION!
The device is not suitable for operation with a frequency converter.
ATTENTION!
When transporting the heat pump, care must be taken to ensure that it is
not tilted more than 45° (in any direction).
ATTENTION!
The heat pump and transport pallet are only joined by the packing film.
ATTENTION!
Do not restrict or block up the area around the air inlet or outlet.
ATTENTION!
Only operate the heat pump with the air ducts connected.
ATTENTION!
Never use cleaning agents containing sand, soda, acid or chloride
because these could damage surfaces.
ATTENTION!
We recommend the installation of a suitable corrosion protection system
to prevent the formation of deposits (e.g. rust) in the condenser of the
heat pump.
ATTENTION!
Before opening the device, ensure that all circuits are isolated from the
power supply.
ATTENTION!
Any work on the heat pump may only be performed by authorised and
qualified after-sales service technicians.
1.2 Legal Regulations and
Directives
The construction and design of the heat pump complies with all
relevant EU directives, DIN/VDE regulations (see CE declaration
of conformity).
When connecting the heat pump to the power supply, the rele-
vant VDE, EN and IEC standards are to be fulfilled. Any further
connection requirements stipulated by local utility companies
must also be observed.
When connecting the heating and/or cooling system, all applica-
ble regulations must also be adhered to.
E-2
1.3 Energy-Efficient Use of the
Heat Pump
With the purchase of this heat pump you are helping to protect
the environment. A prerequisite for energy-efficient operation is
the correct design of the heat source system and heating (radia-
tors and circulation pump) or cooling system.
It is particularly important for the efficient heating operation of a
heat pump to keep the temperature difference between the
heating water and the heat source as small as possible. For this
reason, it is advisable to design the heat source and heating sys-
tem very carefully. A temperature difference of approx. one
Kelvin increases the power consumption by around 2.5 %.
When designing the heating system, it should be borne in mind
that special consumers such as e.g. hot water preparation should
also be considered and dimensioned for low temperatures. Un-
derfloor heating systems (panel heating) are optimally suited
for heat pump use on account of the low flow temperatures
(30 °C to 40 °C).
It is important to ensure that the heat exchangers are not con-
taminated during operation because this increases the tempera-
ture difference, in turn reducing the COP.
Correct adjustment of the heat pump controller is also important
for energy-efficient use of the heat pump. Further information can
be found in the heat pump controller's operating instructions.
2
Purpose of the Heat
Pump

2.1 Application

The air-to-water heat pump is designed for use in existing or
newly built heating systems.
It is designed exclusively for heating and cooling heating water!
In heating operation, the heat pump is suitable for mono energy
and bivalent operation down to an external temperature of
-20 °C.
Proper defrosting of the evaporator is guaranteed by maintaining
a heating water return flow temperature of more than 18 °C dur-
ing continuous operation.
The heat pump is not designed for the increased heat consump-
tion required when a building is being dried out. The additional
heat consumption should be met using special devices provided
by the customer. If a building is to be dried out in autumn or win-
ter, we recommend installing an additional heating element
(available as an accessory).
In cooling operation the heat pump is suitable for temperatures
ranging from +15 °C to +40 °C.
It can be used for silent and dynamic cooling. The minimum
water temperature is +7 °C.
ATTENTION!
The device is not suitable for operation with a frequency converter.