Herunterladen Inhalt Inhalt Diese Seite drucken

Lenze r750-C Montage- Und Einschaltanleitung Seite 52

Rückspeiseeinheit
Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

Electrical installation
Mains connection
3-phase mains connection 400 V
Supply with a power supply module
Fig. 2: Supply with a power supply module and an upstream collective mains filter
R1
Regenerative module r750-C
G1 ... Gx
Interconnected drive systems
L1, L2, L3
Mains connections
Mains filters must be designed for the regenerative feedback mode with block current, e. g.
E94AZMP0494 (49 A, 3x500 V).
When operating inverters in a network, observe the information given in the documentation,
e. g. the maximum number of devices.
The inductance connected between regenerative module and mains must be maximally 0.6
mH.
52
AC
3
AC
3
3
L1
L2
L3
L1
L2
L3
L1.1
L2.1
L3.1
M
Z1
V1
G1
AC
L1
...
M
M
...
Gx
V1
Power supply module
optionally: inverter with power reserve
Z1
Collective mains filter
EMC: conducted, category 2
3
L2
L3
~ =
R1

Quicklinks ausblenden:

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis