Herunterladen Inhalt Inhalt Diese Seite drucken

Csa Certification Record - ABB TZIDC Kurzanleitung

Digitaler stellungsregler
Vorschau ausblenden Andere Handbücher für TZIDC:
Inhaltsverzeichnis

Werbung

28
TZIDC DIGITALER STELLUNGSREGLER | DS/TZIDC-DE REV. C
... Einsatz in explosionsgefährdeten Bereichen

CSA Certification Record

Certificate
Certificate
Class 2258 04
Electrical data
Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner
For use in
Input rated
Output pressure
Intrinsically safe with entity parameters of:
Terminals 11 / 12
Terminals 81 / 82
Terminals 83 / 84
Terminals 31 / 32
Terminals 41 / 42 and 51 / 52
Terminals Limit 2 41 / 42
and Limit 1 51 / 52
When installed per installation Drawing No 901064:
Temperature Code
Max. Ambient temperature
Change from two to one column
1649904 (LR 20312)
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For
Hazardous Locations
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F, and G,
Class III, Div 1, Enclosure Type 4X
30 V DC; max.4 to 20 mA
80 psi (Marine version)
V max = 30 V
C
= 6.6 nF
i
I max = 104 mA
L
= 0 μH
i
P
= 1 W
i
V max = 30 V
C
= 3.7 nF
i
I max = 110 mA
L
= 0 μH
i
P
= 1 W
i
V max = 30 V
C
= 3.7 nF
i
I max = 90 mA
L
= 0 μH
i
P
= 1 W
i
V max = 30 V
C
= 6.6 nF
i
I max = 110 mA
L
= 0 μH
i
P
= 1 W
i
V max = 30 V
C
= 3.7 nF
i
I max = 96 mA
L
= 0 μH
i
P
= 1 W
i
V max = 15.5 V
C
= 20 nF
i
I max = 52 mA
L
= 30 μH
i
P
= 1 W
i
T4
85 °C
Note
The 'x' in P/N denotes minor mechanical variations or
optional features.
Local communication interface LCI shall not be used in
hazardous location.
Each pair of conductors of each intrinsic safety circuit
shall be shielded.
See FM installation drawing No. 901064 for Details.
FM Approvals
TZIDC Positioner, Model V18345-a0b2c2de0f
IS/I,II,III/1/ABCDEFG/T4 Ta = 85 °C – 901064/7/4; Enity;
NI/I/2/ABCD/T4 Ta = 85 °C;
S/II,III/2/FG/T4 Ta =85 °C; Type 4X
Max Enity Parameters: Per Control Drawings
a
Case/mounting – 1, 2, 3, 4 or 9
b Input/communication port – 1 or 2
c
Output/safe protection – 1, 2, 4 or 5
d Option modules for analog or digital position feedback –
0, 1, 3 or 5
e
Mechanical kit (proximity swiches) for digital position
feedback (option) – 0, 1 or 3
f
Design (varnish/coding) – 1 or 2
See FM installation drawing No. 901064 for Details.