3-Phase Mains Connection 230/240 V; Connection Diagrams - Lenze i510-Cabinet Montage- Und Einschaltanleitung

Vorschau ausblenden Andere Handbücher für i510-Cabinet:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

3-phase mains connection 230/240 V

Connection diagrams

The connection plan is valid for the inverter I51AExxxC.
The I51AExxxC inverter does not have an integrated RFI filter in the AC mains supply.
In order to meet the EMC requirements according to EN 61800−3, an external EMC filter according
to IEC EN 60939 must be used.
The user must verify that the conformity with EN 61800−3 is fulfilled.
L1
L2
L3
N
PE
F1
...
F3
3/ PE
Q1
AC
170 V ... 264 V
45 Hz ... 65 Hz
+
+
"
J
J
M
+
3~
Fig. 9: Wiring example
S1
Start/Stop
Fx
Fuses
CANopen/Modbus
Modbus
AC 240 V
3 A
100 mA
Basic I/O
+24 V
+10 V
"
S1
Q1
Mains contactor
---
Dashed line = options
Electrical installation
Mains connection
3-phase mains connection 230/240 V
3/N/ PE
AC
208 V ... 240 V
103