aTEX installation Drawings, UK, FR, DE, DK - 5343a
LERBAKKEN 10, 8410 RØNDE DENMARK.
For safe installation of 5343A the following must be observed. The module shall only be installed
by qualified personnel who are familiar with the national and international laws, directives and
standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
ATEX Certificate
Marking
Standards
T4: -40 ≤ Ta ≤ 85ºC
T6: -40 ≤ Ta ≤ 60ºC
Special conditions for safe use:
For use in a potentially explosive atmosphere of flammable gasses, vapours or mists, the
transmitter shall be mounted in an enclosure providing a degree of protection of at least IP54 in
accordance to EN60529.
For use in the presence of combustible dusts the transmitter shall be mounted in an enclosure
providing a degree of protection of at least IP6X in accordance with o EN60529. The surface
temperature of the enclosure shall be determined after installation of the transmitter.
For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least 20
K above the ambient temperature.
Revision date:
2009-11-17
ATEX Installation drawing
KEMA 10ATEX 0004X
II 3 GD Ex nA [nL] IIC T6..T4
II 3 GD Ex nL IIC T6..T4
II 3 GD Ex nA [ic] IIC T6..T4
II 3 GD Ex ic IIC T6..T4
EN 60079-0 : 2006, EN 60079-11 : 2007, EN 60079-15 : 2005
Terminal: 3,4,6
Ex nA [nL]
Uo: 27 V
Io: 7.0 mA
Po: 45 mW
Lo: 35 mH
Co: 90 nF
Version Revision
V1R0
5343V103-IN
WWW.PRELECTRONICS.COM
Terminal: 1,2
Terminal: 1,2
Ex nA
Ex nL or Ex ic
U ≤ 35 VDC
Ui = 35 VDC
I = 4 - 20 mA
Li = 10 μH
Ci = 1.0 nF
5343QA02
Page:
1/1
51