Herunterladen Inhalt Inhalt Diese Seite drucken

WIKA GDM-100-TI Betriebsanleitung Seite 16

Gasdichtewächter
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

5. Commissioning, operation
Capacitive load
With capacitive loads elevated switch-on currents arise. These can be reduced by
series-connecting resistors in the supply line.
EN
Examples: Contact protection measure with current-limiting resistor
U
B
5.3 Electrical mounting of the transmitter
Requirements for voltage supply
Power supply: DC 10 ... 30 V
The supply must be made via an energy-limited circuit in accordance with IEC 61010-1.
Requirements for electrical connection
Cable diameter matches the cable bushing of the mating connector.
Cable gland and seals of the mating connector are correctly seated.
With cable outlets, no humidity can ingress at the cable end.
Requirement for shielding and grounding
The transmitter is grounded via the process connection of the gas density monitor. The
transmitter is connected with the process connection of the gas density monitor via the
mounting.
Pin assignment
Transmitter, angular connector (2-pin)
16
R
1
Load
UB+/Sig+
+
U
-
0V/Sig-
WIKA operating instructions, models GDM-100-TI, GDM-100-TA
U
B
R
A
1
Load

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Gdm-100-ta

Inhaltsverzeichnis