Commissioning
No.
5
4
3
2
●
●
●
14
*
●
●
●
15
*
○
○
○
16
* *
○
○
●
17
* *
○
○
●
18
* *
○
●
○
19
* *
○
●
○
20
* *
○
●
●
21
* *
○
●
●
22
* *
●
○
○
23
**)
* *
●
○
○
24
**)
* *
●
○
●
25
* *
46
1
Parameter
○
Set battery monitoring
●
Behaviour at internal fault
●
Smoke detector remote resetting
via RWA CLOSE/RESET
○
Alarm reinitiation (VdS 2581)
●
Function Signal relay 1
○
Function Signal relay 2
●
Function Signal relay 3
○
BMZ input
●
Motor runtime
○
Internal vent switch
●
Brightness illumination of inter-
nal RWA switch
○
Motor operating mode
Value
00
Battery monitoring inactive, no display at battery fault
(operation without battery)
01
Battery monitoring active, only display
02
Battery monitoring active, OPEN all windows at fault
03
Battery monitoring active, CLOSE all windows at
fault
00
Only display of the fault
01
Open all windows at power failure
02
Close all windows at power failure
00 / 01
off / on
00 / 01
off / on
00
Alarm
01
Fault (general)
*)
02
Window OPEN
03
Time-limited alarm (300 s)
04
Time-delayed alarm (10 s)
05
Battery fault
06
Detector line fault
07
Motor line fault
08
Power failure
*)
09
"Reset Alarm" as pulse (1 s)
00
Alarm
01
Fault
*)
02
Window OPEN
03
Time-limited alarm (300 s)
04
Time-delayed alarm (10 s)
05
Battery fault
06
Detector line fault
07
Motor line fault
08
Power failure
*)
09
"Reset Alarm" as pulse (1 s)
00
Alarm
01
Fault
*)
02
Window OPEN
03
Time-limited alarm (300 s)
04
Time-delayed alarm (10 s)
05
Battery fault
06
Detector line fault
07
Motor line fault
08
Power failure
*)
09
"Reset Alarm" as pulse (1 s)
00
BMZ latching function
01
Without BMZ latching function (dead-man function)
00 s ... 300 s ... 720 s
max. motor runtime in s
00 / 01
off / on
00
Deactivated
0 ... 10
Brightness changes directly
10 = 100%
00
Motor connection for standard motor
01
Motor connection for retention magnet
Staircase control unit THZ
***)