Technical Data

13.0 Technical Data
Insulation Resistance Measurement
Range
0,005...1,999 MΩ
2...19,99 MΩ
20...199,9MΩ
0,200...1,999GΩ
Nominal Test voltage
100V DC
250V DC
500V DC
1000V DC
Test-Current:.................................................. ≥ 1mA at U N
Short circuit current Is:...................................≤ 2mA
automatic measurement range selection
Low Ohm Measurement
Measurement range:....................................... 0,03..19,99 Ω
Resolution:..................................................... 0,01 Ω
Tolerance:....................................................... ±(3% v.M. +3 Digit)
Open Circuit Voltage:...................................... 5V...9V DC
Test current:....................................................≥ 200mA for resistance < 2Ω
Number of measurements.............................. approx. 1400 (at 1Ω to Lowbat)
Overload protection:........................................600V AC/DC
Fuse:................................................................F500mA/250V
Compensation of Test Lead:
Test lead resistance:
AC/DC Voltage (40...500Hz)
Range
Resolution
0...500V
1
28
Resolution
Tolerance
1 kΩ
10 kΩ
±(5% rdg.. +5 Digit)
100 kΩ
1 MΩ
max. OpenVoltage Uq
UN + 50%
UN + 50%
UN + 50%
UN + 50%
max. 2,00 Ω
Tolerance
±(3% rdg. +3 D)
Overload Protection
1200V AC/DC
number of measurements at (to LowBat)
100kΩ
-
ca. 2500
250kΩ
-
ca. 2000
500kΩ
-
ca. 1400
1 MΩ
-
ca. 600
Overload Protection
Internal Resistance
600V AC/DC
330kΩ