List of functions that can/cannot be used in combination

Schedule
ON/OFF timer
Auto-OFF timer

Auto return

Set temp. range limit

Lock operations
Night setback
Centrally controlled
Energy saving
(Assist function)
: The functions can be used in combination.
1 : The "Schedule" setting is not effective because "ON/OFF timer" has the higher priority.
2 : The "Auto return" function cannot be used because the "Set temp. range limit" setting has the higher
priority.
1 : The "Auto return" function will not be executed when the units are operated in the "Set temperature offset"
mode.
2 : The units cannot be operated in the energy-saving mode if the operation is prohibited from the centralized
controller.
3 : The "Night setback" function will not be executed when the unit has been turned on by "ON/OFF timer."
4 : The "Auto-OFF timer" function will not be executed while the "Night setback" function is executed.
5 : The "Night setback" function will not be executed when the unit has been turned on by "Schedule" settings.
6 : The "Set temp. range limit" settings will not be effective while the "Night setback" function is executed.
7 : The "Auto return" function will not be executed while the "Night setback" function is executed.
8 : The "Energy saving" function will not be executed while the "Night setback" function is executed.
*1 : The events that are prohibited from the centralized controller will not be executed.
78
1
1
5
3
4
*1
*1
*1
: Restricted
: The functions cannot be used in combination.
2
2
7
6
*1
1
5
*1
3
*1
4
*1
7
*1
1
6
1
8
1
2
8
2