Herunterladen Inhalt Inhalt Diese Seite drucken

Mitsubishi Electric CITY MULTI PQRY-P250 Installationshandbuch Seite 29

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 33
4. Remote controller
Check code
6101
Unreadable response receiving error
6600
Duplicated unit address setting
6602
Transmission error (Transmission processor hardware
error)
6603
Transmission error (Transmission route BUSY)
2 Diagnostic switch (SW1) and the service LED on multi-controller board of indoor unit can be used to judge a malfunction of heat source
unit.
<Operation of self-diagnosis switch (SW1) and the service LED display>
Self-diagnosing
SW1 setting
item
Relay output
display 1
A
(Lighting)
B
1 2 3 4 5 6 7 8 9 10
Check
C
a
display 1
(Blinking)
A
Relay output
B
display 2
1 2 3 4 5 6 7 8 9 10
A
Check
B
indoor unit
1 2 3 4 5 6 7 8 9 10
A
Check
B
indoor unit
1 2 3 4 5 6 7 8 9 10
A
Indoor unit
B
mode
1 2 3 4 5 6 7 8 9 10
b
A
Indoor unit
B
mode
1 2 3 4 5 6 7 8 9 10
A
Indoor unit
B
thermostat
1 2 3 4 5 6 7 8 9 10
A
Indoor unit
B
thermostat
1 2 3 4 5 6 7 8 9 10
a Heat source unit
A ON
B OFF
Trouble
Display at LED lighting (blinking) Remarks
Flag 1
Flag 2
Flag 3
During
Crank
compres-
case
21S4
sor run
heater
0000 to 9999 (Alternate display of address and error code)
SV5
SV6
SV71
No.1
No.2
unit
unit
No.9
No.10
No.11
unit
unit
No.1
No.2
unit
unit
No.9
No.10
No.11
unit
unit
No.1
No.2
unit
unit
No.9
No.10
No.11
unit
unit
b Indoor unit
C At factory shipment
Check code
6606
Transmission and reception error (Communication trou-
ble with transmission processor)
6607
Transmission and reception error (No ACK error)
6608
Transmission and reception error (No responsive frame
error)
Flag 4
Flag 5
Flag 6
SV1
SV2
SV3
SV72
SV73
No.3
No.4
No.5
No.6
unit
unit
unit
unit
No.12
No.13
No.14
unit
unit
unit
unit
No.3
No.4
No.5
No.6
unit
unit
unit
unit
No.12
No.13
No.14
unit
unit
unit
unit
No.3
No.4
No.5
No.6
unit
unit
unit
unit
No.12
No.13
No.14
unit
unit
unit
unit
Trouble
Flag 7
Flag 8
Always
SV4
lighting
Flag 8 always lights
at microcomputer
power ON
SSR
No.7
No.8
unit
unit
Lights at emergency
stop in IC and BC
Turns off by resetting
No.15
No.16
unit
unit
No.7
No.8
unit
unit
Lights at cooling
Blinks at heating
Turns off at stop/fan
No.15
No.16
unit
unit
No.7
No.8
unit
unit
Lights at thermostat
on Turns off at
thermostat off
No.15
No.16
unit
unit
29