4.6. Controller operations

Manual operation

In manual operation, the user manually controls the settings of the
installation. The last setting remains active until the user changes it or
until the schedule timer forces another setting (refer to "Schedule
timer operation" on page 8).
As the controller can be used for a wide variety of installations, it is
possible to select a function which is not available on your
installation. In that case the message
Switching on and setting space heating (
(
c
)
1
Use the
=
button to select space heating (
(
c
).
Icon
h
or
c
appears on the display as well as the corresponding
water temperature set point.
2
Use the
bi
and
bj
temperature.
Temperature range for heating: 25°C to 55°C
The temperature for heating can be set as low as 15°C (see
"5. Field settings" on page 13). However, the temperature for
heating should only be set lower than 25°C during
commissioning of the installation. When set lower than 25°C,
only the backup heater will operate.
In order to avoid overheating, space heating is not operable
when the outdoor ambient temperature rises above a certain
temperature (as set through field setting [4-02], refer to
"5. Field settings" on page 13).
Temperature range for cooling: 5°C to 22°C
CAUTION
The actual operation range depends on the values set on
field setting [9].
These values shall be determined based on the
application.
INFORMATION
In heating mode (
h
) or cooling mode (
temperature set point can also be weather dependent (icon
a
is shown).
This means that the controller calculates the water
temperature set point based on the outdoor temperature.
In this case the controller shows the calculated controller
set point. The
bi
button or
display the actual "shift value" and subsequently, to set the
correct value. This shift value is the temperature difference
between the temperature set point calculated by the
controller and the real set point. E.g. a positive shift value
means that the real temperature set point will be higher
than the calculated set point.
3
Switch on the unit by pushing the
The operation LED
0
lights up.
INFORMATION
When the unit is connected to an external room
thermostat, buttons
=
icon
e
is shown. In this case, the external room
thermostat switches the unit on or off and determines the
operation mode (space heating or space cooling).
BelariaS16IE02+BelariaSR16IE02
Indoor unit and options for air to water heat pump system
4PW62581-1 – 10.2010
n
will appear.
h
) and space cooling
h
) or space cooling
buttons to set the desired water
c
), the water
bj
button can be used to
y
button.
and
y
are not operable and the
4 209 847 / 00
Selection and setting of domestic water heating (
1
Use the
v
button to activate domestic water heating (
Icon
w
appears on the display.
2
Use the
wi
or
wj
temperature set point and subsequently, to set the correct
temperature.
The actual temperature set point only appears on the display
after pressing one of the buttons
pressed for 5 seconds, the temperature set point will
automatically disappear from the display again.
Temperature range for domestic water heating: 30°C to 78°C.
INFORMATION
The domestic hot water set point set on the controller
is the actual domestic hot water set point ([4-03]=0, 1,
2, or 3) or the domestic hot water storage set point
([4-03]=4). See "Domestic water heating operation
(w)" on page 6.
v
3
Press the
button to deactivate domestic water heating (
Icon
w
disappears from the display.
INFORMATION
Remark that pushing the
on the domestic water heating. Domestic water
heating is only switched on or off by means of the
v
button.
Selecting powerful domestic water heating operation
1
Press
v
for 5 seconds to activate powerful domestic water
heating operation.
Icons
w
and
m
start flashing.
Powerful domestic water heating is deactivated automatically
when the set point for the domestic hot water is reached.
Selecting quiet mode operation (
1
Use the
s
button to activate quiet mode operation (
Icon
s
appears on the display.
If the controller is set in permission level 2 or 3 (refer to "5. Field
settings" on page 13), the
s
Selecting weather dependent set point operation
1
Press the
ba
button to select weather dependent set point
operation.
Icon
a
appears on the display as well as the calculated water
temperature set point based on the outdoor temperature.
2
Use the
bi
or
bj
button to display the actual shift value
and subsequently, to set the correct value.
The shift value only appears on the display after pressing one of
the buttons
bi
or
bj
. If no button is pressed for 5 seconds,
the shift value will automatically disappear from the display again.
Range for the shift value: –5°C to +5°C
Displaying actual temperatures
ba
1
Push the
button for 5 seconds.
The
b
icon and the entering water temperature are displayed.
The icons
l
and
=
are flashing.
2
Use the
pi
and
pj
buttons to display:
Flashing icon(s)
h
c
or
The entering water temperature
h
c
é
or
and
The outgoing water temperature after plate heat
exchanger
h
c
)
or
and
The outgoing water temperature after backup
heater
ç
The liquid refrigerant temperature
u
The outdoor temperature
w
The domestic hot water temperature
If no button is pressed for 5 seconds, the controller leaves the
display mode.
w
)
w
).
button to display the actual
wi
or
wj
. If no button is
w
y
button has no influence
s
)
s
).
button will not be operable.
Meaning
Operation manual
).
7