Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Boiler House
This must conform to local regulations in particular in terms of
high and low level ventilation, size, fi re resistance etc. Gas fi red
installations must comply with the Gas Safety (Installation and
Use) 1984 Regulations as amended.
A Hight level ventilation
B Low level ventilation
C Draught stabiliser
D Cleanout cover
H Chimney height
I Diameter of chimney
J Internal fl ue connection
Type
Minimum fresch air requirement
High level ventilation
Low level ventilation
Draught stabiliser
Ø of chimney :
Height 5 m.
Height 10 m.
Height 15 m.
Height 20 m.
Oil connection
H
H (m) / Ø in. mm
6
L (m)
0,0
17
0,5
15
1,0
13
1,5
11
2,0
9
2,5
7
3,0
5
3,5
3
Injector / Düse
2,5 kg/h

INSTALLATION

MONTAGE
CA 100
CA 150
m
3
/h
95
133
dm
2
2
2
dm
2
5,7
8
mm.
200
200
mm.
180
210
mm.
150
180
mm.
140
160
mm.
130
150
8
10
L (m)
L (m)
53
100
47
100
41
99
34
84
28
68
22
53
15
37
9
22
5,0 kg/h
10,0 kg/h
Heizungsraum
Der Heizungsraum muß den jeweiligen lokalen Vorschriften
in puncto Abmessungen, Hitzebeständigkeite der Wände,
Stahltüren, Kamine sowie Be- und Entlüftung entsprechen.
A Belüftung
B Entlüftung
C Zugregler
D Schauloch
H Kaminhöhe
I Kamindurchmesser
J Anschlußstück
CA 200
Typ
224
Minimale Luftzufuhr
2
Belüftung
13
Entlüftung
200
Zugregler
Ø des Kaminanschlusses :
270
Höhe 5 m.
230
Höhe 10 m.
210
Höhe 15 m.
200
Höhe 20 m.
Ölversorgung
H
H (m) / Ø in. mm
4
4,0
51
2,5
45
3,0
38
2,5
32
2,0
26
1,5
19
1,0
13
0,5
6
Injector / Düse
2,5 kg/h
m
3
/h
dm
2
dm
2
mm.
mm.
mm.
mm.
mm.
6
4
6
6
8
L (m)
L (m)
L (m)
100
26
100
65
100
100
22
100
57
100
100
19
97
49
100
100
16
81
40
100
100
13
65
32
100
97
10
49
24
77
65
6
32
16
51
32
3
16
8
26
5,0 kg/h
10,0 kg/h
7

Werbung